F
AULT
M
ESSAGES
, P
OWER
G
EN
121
2024
‘Duct Jacket’ temperature
critical
Temperature on the cooled
exhaust duct is above
230°F/110°C
• If sensor readings are
unstable, verify sensor
seated well. Replace
sensor.
• Check for flow reading
and pump feedback.
2025
Burner blower not spinning
Blower not getting power,
signal harness unplugged.
blower seized or damaged,
• Verify disconnect switch
in '1' position
• Inspect all fuses on FPC.
• If pump feedback is zero,
check QEC output C
configuration.
• Inspect harnesses and
connectors are firmly
seated. Replace if
necessary.
• Replace blower.
• Replace FPC.