C
OMMISSIONING
P
ROCEDURE
105
Table 12-11 Modbus, ENUM
Register
Name
Value
Description
40042 - Input
functions for
assigning to input
channel selected in
40041
UNUSED
0
START_STOP
1
Unit will start if selected input
channel is shorted. Will stop if
the channel is opened
START
2
Unit will start if selected input
channel is shorted.
STOP
3
Unit will stop if selected input
channel is shorted.
LOAD_DISCONN_CONN
4
Load disconnect relay will
open if selected input channel
is shorted.
CLEAR_WARNINGS
5
All warnings will b cleared if
selected input channel is
shorted.