C
OMMISSIONING
P
ROCEDURE
106
40044 - Output
function for assigning
to output channel
selected in 40043
ENABLED
1
Close if engine is enabled or
disabling.
RUNNING
2
Close if engine is running
(power>0W).
FAULT
3
Close if there is a fault active.
WARNING
4
Close if there is an active
warning.
ESTOP_ACTIVE
5
Close if e-stop is active.
LOAD_CONNECTED
6
POWER_GT_2500
7
Close when power>2500W,
open when power drops
below 2200W.
POWER_GT_5500
8
Close when power>5500W,
open when power drops.
FAULT_IGNITION
8
Close when burner ignition
fault is active.
FAULT_GAS_PRESSURE
9
Close when gas pressure is
below 12mbar, open
automatically when pressure
rises above 20mbar.
FAULT_COOLANT_LOW
10
Close when overflow tank is
2/3 empty.
FAULT_TEMP_HI
11
Close when ambient temp
exceeds 55°C, open when
temp drops below 50°C
FAULT_TEMP_LO
12
FAULT_FLOW_LOW
13
Close if coolant flow went
below 20lpm
FAULT_BATT_LOW
14
Table 12-11 Modbus, ENUM
Register
Name
Value
Description