C
OMMISSIONING
P
ROCEDURE
80
Figure 12-9 Helium Tank
6. PURGE any residual air from the Kit.
NOTE: Pressure gauges only display PSI.
7. Tighten the regulator (clockwise).
8. Pressurize the fill kit to 100 PSI.
9. Loosen the regulator (anti-clockwise).
10.Reduce pressure to 30psi through self-venting of the regulator.
11. Repeat steps 7. on 80and 9. on 80 to ensure that air in the flexible hose is diluted and
washed out of the kit by purging with pressurized Helium.
Figure 12-10 Helium Kit, Purge
12.5.3 PRESSURIZE AN ENGINE
Following PREPARATION, attach the Staubli Socket to an engine that needs filling. Depending on
conditions, some gas may begin flowing into or out of the engine.