Internal circulating pump load
is out of range
Pump feedback is outside
expected power draw range
during initial startup test. Air in
the cooling system, pump
friction, incorrect glycol
concentration on cold
startups.
• If pump runs and
feedback fluctuates more
than 1%, look for leaks
and perform coolant fill
procedure.
• Loosen blocked pump, If
serial number is below
PG260 and has a gold
color coolant in it, flush
out coolant with Preston
AF2000 Core-guard
50/50 for standard
PowerGen and 60/40
concentration for LTS
PowerGen.
• If coolant is below +10°C
and feedback is above
40%, Test glycol
concentration in coolant.
• Replace pump.