11.3.4 FPC Expansion Board
The PowerGen has six (6) discrete inputs and eight (8) relay outputs. Discrete inputs and relay
outputs are configured as follows in Table 11-3 and Table 11-4. See Table 12-2 on page 96 and
Table 12-3 on page 97 for more details on the selectable options.
•
Note:
The disable/enable function within Qnergy Lynx and e-stop will override any
remote signal. LUI enable/disable push button will not function while in remote mode.
Further information can be found in see Section 12.9
Table 11-3 PowerGen FPC Expansion Board Input Description
Discrete Inputs
No.
Default
Selectable Options
1 thru 6
Unused
• System Toggle (Enable/Disable)
• System Enable
• System Disable
• Load Disconnect/Connect
• Clear Warnings
Table 11-4 PowerGen FPC Expansion Board Output Description
Relay Outputs
No.
Default
Selectable Options
1 through 8
Unused
• System enabled
• Engine running
• System in fault
• System has warnings
• Estop activated
• Power >2500W
• Power>5500W
• Burner ignition fault
• Gas Pressure low
• Coolant low
• Tamb above limit
• Tamb below limit
• Coolant low flow
Summary of Contents for PowerGen 5650 Series
Page 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Page 8: ...iv...
Page 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Page 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Page 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Page 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Page 194: ...POWERGEN OPTIONAL FEATURE SETS 182...