F
AULT
M
ESSAGES
, P
OWER
G
EN
136
11005
Hall watchdog timer has
expired
• Update QEC firmware to
3.2.1 or later
• Problem with the engine
hall sensors
• Bad engine connection
11006
No hall pulses measured
• Problem with the engine
hall sensors
• Bad engine connection
11007
Brake current greater than
hardware limit
QEC hardware failure
11008
Output A circuit failed
QEC hardware failure
11009
Output B circuit failed
QEC hardware failure
11010
Output C circuit failed
QEC hardware failure
11011
Abnormal total power balance
QEC hardware failure
11012
Failed to start
Helium pressure is low,
problem with the heat source
11013
Hall fit quality poor
Hall switch point calibration is
wrong, problem with the
engine hall sensors
11014
Engine frequency is above or
below expected value
Hall switch point calibration is
wrong, problem with the
engine hall sensors, incorrect
engine pressure
12001
Positive or negative DC buses
fail to reach setpoint during
BBI operation
Low battery, faulty battery
12002
Positive bus voltage too low
Low battery, faulty battery
12003
Positive bus voltage ripple too
high
QEC hardware failure
12004
Negative bus voltage too low
Low battery, faulty battery
12005
Negative bus voltage ripple
too low
QEC hardware failure
Table 15-8 QEC Error Messages, QEC 3.5 (Firmware 3.X.X)
Fault Code
Description
Possible Causes
Summary of Contents for PowerGen 5650 Series
Page 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Page 8: ...iv...
Page 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Page 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Page 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Page 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Page 194: ...POWERGEN OPTIONAL FEATURE SETS 182...