C
OMMISSIONING
P
ROCEDURE
88
Figure 12-18 Qnergy Lynx, QEC, Configuration Tab, Minimum Engine Power
10.Allow up to 5 minutes for the unit head temperature to stabilize.
11. The Lambda reading should be 1.18 +/- 0.01.
12. To
decrease
Lambda, turn screw #3
counter-clockwise
(see Figure 12-10).
13. To
increase
Lambda, turn screw #3
clockwise
(see Figure 12-10).
14.Under the QEC/Config Tab, Set
Minimum Engine Power to 600W
, Click Set, Allow 1 minute for
unit to stabilize. Lambda reading should be 1.23 +/- 0.01.