P
OWER
G
EN
O
PTIONAL
F
EATURE
S
ETS
180
Connections to the enclosure are made to the field wiring terminals (Figure 21-9, “5”), as
detailed in below in Table 21-6.
Table 21-6 Field Wiring Terminals
Position
Designation
Wire Gauge
Torque
X1 - Input
GND
GND/PE
20-6 AWG
0.5-16 mm²
13.3-16 lbf*in
1.5-1.8 Nm
1
PowerGen A Common (Neutral)
2
PowerGen A L1
3
PowerGen A L2
4
PowerGen B Common (Neutral)
5
PowerGen B L1
6
PowerGen B L2
GND
GND/PE
X2 - Output
GND
GND/PE
20-6 AWG
0.5-16 mm²
13.3-16 lbf*in
1.5-1.8 Nm
1
Common (Neutral)
2
L1
3
L2
X3 - Control
1
PowerGen A Enable Input
20-6 AWG
0.5-16 mm²
13.3-16 lbf*in
1.5-1.8 Nm
2
3
PowerGen B Enable Input
4
WARNING:
All electrical connections are to be made
with all sources of energy removed following all local
and company Lockout/Tagout procedures.