Figure 9-1 PowerGen Mounting Dimensions
The maximum allowed slope is 2.5%. PowerGen should be located such that the long plane is
parallel to the slope direction and that the radiator fill cap is elevated above the generator.
The PowerGen is not intended to be operated in a marine, hazardous, or chemical intensive
environments. A marine-rated PowerGen is available. Contact your distributer for more
information.
9.2 GAS SUPPLY
The gas supply inlet is fitted with 1/2” NPT male fitting.
The minimum pressure (Natural Gas) should be:
• 3PSIG
The maximum pressure (Natural Gas) should be:
• 50PSIG
A flexible gas line of at least two feet must be used to connect the RP to a rigid fuel supply
line.
WARNING:
Danger of death by gas escape if the
gas supply is not properly installed. The gas supply
must only be installed by a qualified technician. All
local regulations for fuel supply must be observed.