C
OMMISSIONING
P
ROCEDURE
84
Note: Prior to commissioning the PowerGen please verify that the Qnergy Lynx, QEC
Load-following parameters are set-up correctly, per the customer electrical load see
Table 12.11.
Note: The PowerGen is factory set and tested to Natural Gas. If application requires the use of
Propane (LPG), turn screw #3 clockwise 3 turns prior to enabling the PowerGen.
1. Verify that the customer gas pressure is within the acceptable range:
• NG, 3 – 50 PSI₂ (customer side)
• Propane, 2 – 10 PSI (customer side)
• From the FPC screen >32mbar (after internal regulator)
Figure 12-13 Blower Tuning Screws
WARNING:
Gas valve tuning should be carried out
by Qnergy-approved technicians only.