12-4
Section
*
*
Error
Correction
Problem
Error code
Manual CCW limit
5071
The internal CCW limit was reached and
feeding stopped during execution of HIGH-
SPEED JOG, LOW-SPEED JOG, or INCH.
Feed clockwise.
ORIGIN SEARCH
not possible
5100
•
ORIGIN SEARCH cannot be executed be-
cause of data for the origin compensation,
search speeds, origin return speeds, or
backlash compensation that generated an
alarm code.
•
ORIGIN SEARCH cannot be executed be-
cause the external input protect is ON.
•
ORIGIN SEARCH cannot be executed be-
cause the CW/CCW limit input was turned
ON at the same time.
•
Read out alarm code and correct
data accordingly.
•
Turn OFF the external input protect
and execute ORIGIN SEARCH
again.
•
Check the CW/CCW limit input wir-
ing.
ORIGIN RETURN
not possible
5200
ORIGIN RETURN cannot be executed be-
cause of data for ORIGIN RETURN speed
or backlash compensation that generated
alarm.
Read out alarm code and correct
and correct data accordingly. The
error code will be cleared for the
next operation if data has been
l
d
HIGH-SPEED JOG
not possible
5300
HIGH-SPEED JOG cannot be executed
because of data for HIGH-SPEED JOG
speed, initial speed, acceleration, decelera-
tion, or backlash compensation that gener-
ated an alarm.
e t o e at o
data as bee
properly corrected.
LOW-SPEED JOG
not possible
5400
LOW-SPEED JOG cannot be executed be-
cause of data for LOW-SPEED JOG
speed, initial speed, or backlash com-
pensation that generated an alarm.
INCHING not pos-
sible
5500
INCH cannot be executed because of data
for backlash compensation that generated
an alarm.
Emergency stop
performed
6000
Feeding has been stopped by emergency
stop signal input.
Feeding was stopped during an origin
search because of chattering.
Check wiring. Turn off emergency
stop signal and execute RELEASE
PROHIBIT and ORIGIN SEARCH.
Stop for CW limit
6100
Feeding has been stopped by CW limit sig-
nal input.
Check wiring. Execute RELEASE
PROHIBIT and then feed counter-
clockwise using HIGH-SPEED
JOG, LOW-SPEED JOG, or INCH
(or execute ORIGIN SEARCH or
RESET PRESENT POSITION after
RELEASE PROHIBIT).
Stop for CCW limit
6101
Feeding has been stopped by CCW limit
signal input.
Check wiring. Execute RELEASE
PROHIBIT and then feed clockwise
using HIGH-SPEED JOG, LOW-
SPEED JOG, or INCH (or execute
ORIGIN SEARCH or RESET
PRESENT POSITION after RE-
LEASE PROHIBIT).
No origin proximity
signal
6200
No proximity signal is detected between the
CCW and CW limits even though the DIP
switch setting designates a proximity sig-
nal.
When ORIGIN SEARCH is executed while
the CW/CCW limit input is ON, the proximi-
ty signal is already ON at the initial posi-
tion.
The proximity signal is sought within the
limit signal range.
Check proximity signal wiring and
signal type (N.C. or N.O.).
Summary of Contents for SYSMAC C500-NC113
Page 1: ...Cat No W323 E3 1 Position Control Units SYSMAC C500 NC113 C500 NC211 OPERATION MANUAL...
Page 2: ...0 1 1 2 304 2 1 3 1 3 1 1 1...
Page 5: ...8 0...
Page 9: ...8 8 0 8...
Page 24: ...0 1...
Page 31: ...0 4 4 4 2 1 2 2...
Page 52: ...8 8 0...
Page 57: ...5 1 Section Acceleration Deceleration Pattern Edit Screen Dwell Time Data Edit Screen...
Page 107: ...0 00 C D 0 0 0 0 E 4 8 3 3 1 3 1 3 1 1 1...
Page 119: ...0 8 1 6...
Page 207: ...1 6 1 1 0 1 1 0 1 1 1 1 1 1 3 1 7 1 3 1 1 8 3...
Page 220: ...4 4 0 1 9 3...
Page 224: ...0 8 6 6...
Page 246: ...01 1 3 2 D 2 0 1 01 1 6 9 0 1 2 2 2 E 0 3 9 2 2 F H 69 9 2 4 54 60 7 5 2 I 4 2 7 2 3 2 69 0 2...
Page 247: ...J L 2 3 60 7 5 M N 2 0 1 6 9 2 O 2 2 2 2 5 91 2 5 6 4 2 2 2 P 0 0 87 87...
Page 248: ...2 2 2 2 9 4 2 0 R 7 6 0 4 9 6 9 0 6 9 0 6 9 S 2 2 2 2 6 6 2 A 2 B 2 2 69 0 3 3 3 2 T 9 4 2...
Page 249: ...W Z 2 2...