7-7
Section
I/O Comment Table
301
Handling of I/O comments of Timer / Counter
Timer/Counter do not have their own number. They share common Timer/Count-
er number.
However, with an I/O comment table at Support Tool, it is possible to input Timer
and Counter separately.
So when the Timer/Counter number is imported, I/O comment table stores the
same comment both for timer and counter of the same number.
In case I/O comment table at Support Tool has an existing I/O comment for either
of timer and counter, existing I/O comment in Support Tool (in I/O comment table)
takes priority and imported I/O comment will be stored only for an empty one.
Example: Existing I/O comment in Support Tool (in I/O comment table)
Word / Bit
I/O Comment
TIM002
AAA
CNT002
BBB
CNT003
CCC
I/O comments in ladder program to be imported
Word / Bit
I/O Comment
TIM/CNT000
DDD
TIM/CNT002
EEE
TIM/CNT003
FFF
TIM/CNT004
GGG
↓
Existing I/O comments in Support Tool (in I/O comment table) after importing
*: Existing I/O comment in Support Tool (in I/O comment table)
Import Procedure
SYSMAC Support Software, SYSMAC CPT
Follow the procedure below to import I/O comment from ladder program.
(1) Select “Import I/O Comments” from the Tools menu.
Dialog box to specify I/O comment is displayed.
(2) Specify the I/O comment file (.SP1) to be imported and click the
Button.
I/O comment Import is performed. While importing, progress will be dis-
played on status bar.