2. Tool magazine counting switch abnormality.
3. Reset the values of the T102 and T103.
(Refer to the details operation: Section Three The Usage and Maintenance of the GSK218MC
Series with Disk Tool-magazine)
Alarm information: 1241 Tool case vertical direction detection abnormality (A005.1)
Fault reason: The tool case vertical direction detection switch (X5.1) does not operate within the
setting time of the T101 when performing the tool case vertical direction operation
(that is: Y3.2=1).
Troubleshooting: 1. Check whether the vertical direction detection switch of the tool case is normal.
2. Check whether the Y3.2 is output.
3. Readjust the time of the T104.
Alarm information: 1242 Tool case horizontal detection abnormality (A005.2)
Fault reason: The tool case horizontal direction detection switch (X5.2) does not operate within the
setting time of the T105 when performing the tool case horizontal direction operation
(that is: Y3.3=1).
Troubleshooting: 1. Check whether the horizontal detection switch of the tool case is normal.
2. Check whether the Y3.3 is output.
3. Readjust the time of the T105.
Alarm information: 1243 Enabled setting of the tool magazine zero position (A005.3)
Fault reason: This alarm occurs when K010.6=1 in the case of the tool magazine is without the zero
return switch (that is: K010.1=0); the tool magazine zero prompts the enabled setting.
Troubleshooting: Set the K010.6 to 0.
(Refer to the details operation: Section Three The Usage and Maintenance of the
GSK218MC Series with Disk Tool-magazine)
Alarm information: 1244 Confirm the tool magazine is normal when tool-change stops abnormally
(A005.4)
Fault reason: When the tool magazine is performed automatic tool-change, the abnormality occurs
so that the tool-change stops or check the manipulator does not at the origin when
starting the system, the alarm then occurs; this alarm is only shown that the operator
tool magazine and the tool number on the spindle may be disorder already. The tool
magazine may not normal after eliminating this alarm; it is better to set the tool
magazine and the tool number on the spindle.