GSK218MC Series Machining Center CNC System PLC&Installation Connetion Manual
256
Appendix
Alarm information: 1212 Excessive low of the pressure grease
Fault reason: User self-defined
Troubleshooting:
Alarm information: 1213 Fail to ready for the machine tool (A001.5)
Fault reason: User self-defined
Troubleshooting:
Alarm information: 1214 Spindle shifting abnormal, fail to rotate (A001.6)
Fault reason: The spindle gear abnormality is detected when the spindle is performed rotation code.
Troubleshooting: The gear I in-position detection switch (X4.1) does not close within the setting time
of the T0021 when the spindle changes the gear I (that is, Y3.4=1); adjust the time
of the T0021 or check whether the X4.1 is closed. The gear I in-position detection
switch (X4.2) does not close within the setting time of the T0022 when the spindle
changes the gear II (that is, Y3.5=1); adjust the time of the T0022 or check whether
the X4.2 is closed. The gear I in-position detection switch (X4.3) does not close
within the setting time of the T0023 when the spindle is placed at the gear III (that is,
Y3.6=1); adjust the time of the T0023 or check whether the X4.3 is closed.
Alarm information: 1215 Firstly perform T code before executing the M06 code (A001.7)
Fault reason: Fail to execute the enabled T code when perform M06 code.
Troubleshooting: Execute the M06 code after perform the enabled T code.
Alarm information: 1216 Cutter releasing, fail to rotate the spindle (A002.0)
Fault reason: The spindle rotation code is performed when tool is on the releasing state, for example:
M03, M04 and M19 will cause the spindle rotation by pressing the spindle positive,
negative, JOG, positioning or AUTO state in the manual mode.
Troubleshooting: Press the “Clamping/Releasing” button in the manual state, so that it is on the
clamping state (that is: Y0.2=0); check whether the state of the cutter clamping
detection switch (X2.6) is set to 1. This alarm will not occur when rotating the
spindle in the state of 1.
Alarm information: 1217 Fail to release the tool when spindle rotation (A002.1)
Fault reason: Tool releasing code is performed when spindle is on the rotation state.
Troubleshooting: Performing the tool releasing code can be avoided this alarm when the spindle is
on the stop state.
Alarm information: 1218 Tool magazine abnormal stop, confirm the tool number again (A002.2)