Alarm information: 1218 Tool magazine abnormal stop, confirm the tool number again (A002.2)
Fault reason: This alarm will be generated after the alarm occurs or the “Reset” button is controlled
when performing the Txx code and the tool magazine is being rotated.
Troubleshooting: 1. Tool magazine zero return again.
2. Reset the tool numbers both spindle and tool magazine.
(Refer to the details operation: Section Three The Usage and Maintenance of the GSK218MC
Series with Disk Tool-magazine)
Alarm information: 1219 Fail to rotate the spindle because the manipulator is not at the origin
(A002.3)
Fault reason: Perform the spindle rotation because the manipulator is not at the origin position.
Troubleshooting: 1. Manipulator returns to the origin position (Check whether the manipulator is on
the origin position by inspecting the state of the X3.4).
2. It is convenient to debug when the manipulator is abnormally stopped during the
operation; the manipulator can be performed the orientation in the mechanical
zero. it is necessary to perform the mechanical zero return firstly when
manipulator is not at the origin, and then perform the orientation.
(Refer to the details operation: Section Three The Usage and Maintenance of the GSK218MC
Series with Disk Tool-magazine)
Alarm information: 1220 Spindle tool clamping detection abnormality (A002.4)
Fault reason: When performing the tool-clamping motion (that is: Y0.2=0), the tool magazine
clamping detection switch (X2.6) does not close within the setting time of the T010.
Troubleshooting: 1. Check whether the tool-clamping detection switch is normal.
2. Check whether the Y0.2 is output.
3. Readjust the time of T010.
Alarm information: 1221 Spindle tool-releasing detection abnormality (A002.5)
Fault reason: When performing the tool-releasing motion ((that is: Y0.2=1), the tool magazine
releasing detection switch (X2.5) does not close within the setting time of the T009.
Troubleshooting: 1. Check whether the tool magazine releasing inspection switch is normal.
2. Check whether the Y0.2 is output.
3. Readjust the time of T009.
Alarm information: 1222 Spindle unit temperature detection abnormality (A002.6)
Fault reason: User self-defined