ADDENDUM
a) SLG FAULT
An AG fault occurs close to the considered relay. Immediately after the fault, the disturbance detector (50DD) picks-up and
activates the phase selector. The phase selector recognizes an AG fault by asserting its PHASE SELECT AG operand.
Ground distance zone 1 (AG element) responds to the fault.
At this moment, the request to trip is placed for the trip output. As the fault is recognized as an AG fault, the TRIP PHASE A
operand is asserted by the trip output. This signal is passed to the breaker control scheme and results in tripping pole A of
the breaker.
Table 0–1: DIRECTIONAL MHO PHASE DISTANCE FUNCTIONS
CHARACTERISTIC
COMPARATOR INPUTS
LIMIT ANGLE
Variable mho
I
×
Z – V
V_1M
COMP LIMIT
Reactance
I
×
Z – V
I
×
Z
COMP LIMIT
Directional
I
×
Z
D
V_1M
DIR COMP LIMIT
Fault type
NOT SLG
Removed during open pole conditions
Table 0–2: DIRECTIONAL QUADRILATERAL PHASE DISTANCE FUNCTIONS
CHARACTERISTIC
COMPARATOR INPUTS
LIMIT ANGLE
Reactance
I
×
Z – V
I
×
Z
COMP LIMIT
Directional
I
×
Z
D
V_1M
DIR COMP LIMIT
Right Blinder
I
×
Z
R
– V
I
×
Z
R
90°
Left Blinder
I
×
Z
L
– V
I
×
Z
L
90°
Fault type
NOT SLG
Removed during open pole conditions
Table 0–3: NON-DIRECTIONAL MHO PHASE DISTANCE FUNCTIONS
CHARACTERISTIC
COMPARATOR INPUTS
LIMIT ANGLE
Offset mho
I
×
Z – V
V-I
×
Z
REV
COMP
LIMIT
Fault type
NOT SLG
Removed during open pole conditions
Table 0–4: NON-DIRECTIONAL QUADRILATERAL PHASE DISTANCE FUNCTIONS
CHARACTERISTIC
COMPARATOR INPUTS
LIMIT ANGLE
Forward Reactance
I
×
Z – V
I
×
Z
COMP LIMIT
Reverse Reactance
I
×
Z
REV
– V
I
×
Z
REV
COMP LIMIT
Right Blinder
I
×
Z
R
– V
I
×
Z
R
90°
Left Blinder
I
×
Z
L
– V
I
×
Z
L
90°
Fault type
NOT SLG
Removed during open pole conditions
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...