GE Multilin
T60 Transformer Protection System
5-187
5 SETTINGS
5.6 GROUPED ELEMENTS
5
Figure 5–75: QUADRILATERAL DISTANCE CHARACTERISTIC SAMPLE SHAPES
•
PHS DIST Z1 XFMR VOL CONNECTION:
The phase distance elements can be applied to look through a three-phase
delta-wye or wye-delta power transformer. In addition, VTs and CTs could be located independently from one another
at different windings of the transformer. If the potential source is located at the correct side of the transformer, this set-
ting shall be set to “None”.
This setting specifies the location of the voltage source with respect to the involved power transformer in the direction
of the zone. The following figure illustrates the usage of this setting. In section (a), zone 1 is looking through a trans-
former from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), Zone 3 is
looking through a transformer from the wye into the delta winding. Therefore, the Z3 setting shall be set to “Yd1”. The
zone is restricted by the potential point (location of the VTs) as illustrated in Figure (e).
•
PHS DIST Z1 XFMR CUR CONNECTION:
This setting specifies the location of the current source with respect to the
involved power transformer in the direction of the zone. In section (a) of the following figure, zone 1 is looking through
a transformer from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), the
CTs are located at the same side as the read point. Therefore, the Z3 setting shall be set to “None”.
See the
Theory of operation
chapter for more details, and the
Application of settings
chapter for information on calcu-
lating distance reach settings in applications involving power transformers.
837723A1.CDR
X
R
R
EAC
H
RCA
= 80
o
COMP LIMIT
= 90
o
DIR RCA
= 80
o
DIR COMP LIMIT = 90
o
RGT BLD RCA
= 80
o
LFT BLD RCA
= 80
o
X
R
X
R
X
R
R
EAC
H
RCA
= 80
o
COMP LIMIT
= 90
o
DIR RCA
= 80
o
DIR COMP LIMIT = 60
o
RGT BLD RCA
= 80
o
LFT BLD RCA
= 80
o
R
EAC
H
RCA
= 90
o
COMP LIMIT
= 90
o
DIR RCA
= 45
o
DIR COMP LIMIT = 90
o
RGT BLD RCA
= 90
o
LFT BLD RCA
= 90
o
R
EAC
H
RCA
= 80
o
COMP LIMIT
= 80
o
DIR RCA
= 45
o
DIR COMP LIMIT = 60
o
RGT BLD RCA
= 80
o
LFT BLD RCA
= 80
o
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...