T60 Transformer Protection System
5-75
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.9 DATA LOGGER
PATH: SETTINGS
PRODUCT SETUP
DATA LOGGER
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to EnerVista UR Setup and displayed with
parameters
on the vertical axis and
time
on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.
Changing any setting affecting data logger operation will clear any data that is currently in the log.
DATA LOGGER
DATA LOGGER MODE:
Continuous
Range: Continuous, Trigger
MESSAGE
DATA LOGGER TRIGGER:
Off
Range: FlexLogic operand
MESSAGE
DATA LOGGER RATE:
60000 ms
Range: 15 to 3600000 ms in steps of 1
MESSAGE
DATA LOGGER CHNL
1:
Off
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
MESSAGE
DATA LOGGER CHNL
2:
Off
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
MESSAGE
DATA LOGGER CHNL
3:
Off
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
↓
MESSAGE
DATA LOGGER CHNL 16:
Off
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
MESSAGE
DATA LOGGER CONFIG:
0 CHNL x
0.0 DAYS
Range: Not applicable - shows computed data only
Table 5–10: DATA LOGGER STORAGE CAPACITY EXAMPLE
SAMPLING RATE
CHANNELS
DAYS
STORAGE CAPACITY
15 ms
1
0.1
954 s
8
0.1
120 s
9
0.1
107 s
16
0.1
60 s
1000 ms
1
0.7
65457 s
8
0.1
8182 s
9
0.1
7273 s
16
0.1
4091 s
60000 ms
1
45.4
3927420 s
8
5.6
490920 s
9
5
436380 s
16
2.8
254460 s
3600000 ms
1
2727.5
235645200 s
8
340.9
29455200 s
9
303
26182800 s
NOTE
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...