GE Multilin
T60 Transformer Protection System
9-5
9 COMMISSIONING
9.2 DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES
9
b) TEST FOR ZERO DIFFERENTIAL CURRENT
1.
Inject the following currents into the relay:
2.
These are determined as follows:
(EQ 9.7)
From the Current Distribution diagram above, there is a
secondary current for HV
phases B and C, and a
secondary current for LV phases b and c.
3.
The relay should display the following differential and restraint currents and the element should not operate:
c) MINIMUM PICKUP TEST
Reduce the restraint current
I
r
to a value lower than 0.67 pu (the restraint corresponding to the intersection of Slope 1 and
the pickup). This is obtained from
, where 0.1 is the differential setting of minimum pickup, and
0.15 is the setting of Slope 1. Note that
(EQ 9.8)
where I
ri
is an intersection of Minimum PKP and Slope 1 calculated as PKP/Slope 1 value.
4.
Change the current magnitude as follows:
5.
The following differential and restraint current should be read from the T60 actual values menu:
The relay will not operate since
I
d
is still lower that the 0.1 pu MINIMUM PICKUP setting.
6.
Increase
I
1
to 0.2 A. The differential current increases to
and
.
7.
Verify that the Percent Differential element operates and the following are displayed in the actual values menu:
WINDING 1
WINDING 2
PHASE SINGLE CURRENT (I
1
)
PHASE SINGLE CURRENT (I
2
)
A
0 A
∠
0°
A
0 A
∠
0°
B
0.434 A
∠
0°
B
0.8 A
∠
–180°
C
0.434 A
∠
–180°
C
0.8 A
∠
0°
PHASE DIFFERENTIAL CURRENT (I
d
)
PHASE RESTRAINT CURRENT (I
r
)
A
0
∠
0°
A
0
∠
0°
B
0
∠
0°
B
0.801 pu
∠
–180°
C
0
∠
0°
C
0.801 pu
∠
0°
WINDING 1
WINDING 2
PHASE SINGLE CURRENT (I
1
)
PHASE SINGLE CURRENT (I
2
)
A
0 A
∠
0°
A
0 A
∠
0°
B
0.15 A
∠
0°
B
0.23 A
∠
–180°
C
0.15 A
∠
–180°
C
0.23 A
∠
0°
PHASE DIFFERENTIAL CURRENT (I
d
)
PHASE RESTRAINT CURRENT (I
r
)
A
0
∠
0°
A
0
∠
0°
B
0.044 pu
∠
0°
B
0.275 pu
∠
–180°
C
0.044 pu
∠
0°
C
0.275 pu
∠
0°
PHASE DIFFERENTIAL CURRENT (I
d
)
PHASE RESTRAINT CURRENT (I
r
)
A
0
∠
0°
A
0
∠
0°
B
0.136
∠
0°
B
0.367 pu
∠
–180°
C
0.136
∠
0°
C
0.367 pu
∠
0°
I
n
w
1
(
)
20 10
6
×
VA
3 115 10
3
×
V
×
---------------------------------------------
100.4 A,
I
n
w
2
(
)
20 10
6
×
VA
3 12.47 10
3
×
V
×
--------------------------------------------------
925.98 A
=
=
=
=
0.866 pu 100.4 A 200
⁄
×
0.434 A
=
0.866 pu 925.98 A 1000
⁄
×
0.8 A
=
I
r
0.1 0.15
⁄
0.67 pu
=
=
0
I
r
I
ri
< <
I
d
0.136 pu Min PKP
>
=
I
r
0.67 pu
<
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...