GE Multilin
T60 Transformer Protection System
5-331
5 SETTINGS
5.9 TRANSDUCER INPUTS AND OUTPUTS
5
5.9.3 RRTD INPUTS
a) MAIN MENU
PATH: SETTINGS
TRANSDUCER I/O
RRTD INPUTS
Menus are available to configure each of the remote RTDs.
Table 5–38: RTD TEMPERATURE VS. RESISTANCE
TEMPERATURE
RESISTANCE (IN OHMS)
°C
°F
100
Ω
PT
(DIN 43760)
120
Ω
NI
100
Ω
NI
10
Ω
CU
–50
–58
80.31
86.17
71.81
7.10
–40
–40
84.27
92.76
77.30
7.49
–30
–22
88.22
99.41
82.84
7.88
–20
–4
92.16
106.15
88.45
8.26
–10
14
96.09
113.00
94.17
8.65
0
32
100.00
120.00
100.00
9.04
10
50
103.90
127.17
105.97
9.42
20
68
107.79
134.52
112.10
9.81
30
86
111.67
142.06
118.38
10.19
40
104
115.54
149.79
124.82
10.58
50
122
119.39
157.74
131.45
10.97
60
140
123.24
165.90
138.25
11.35
70
158
127.07
174.25
145.20
11.74
80
176
130.89
182.84
152.37
12.12
90
194
134.70
191.64
159.70
12.51
100
212
138.50
200.64
167.20
12.90
110
230
142.29
209.85
174.87
13.28
120
248
146.06
219.29
182.75
13.67
130
266
149.82
228.96
190.80
14.06
140
284
153.58
238.85
199.04
14.44
150
302
157.32
248.95
207.45
14.83
160
320
161.04
259.30
216.08
15.22
170
338
164.76
269.91
224.92
15.61
180
356
168.47
280.77
233.97
16.00
190
374
172.46
291.96
243.30
16.39
200
392
175.84
303.46
252.88
16.78
210
410
179.51
315.31
262.76
17.17
220
428
183.17
327.54
272.94
17.56
230
446
186.82
340.14
283.45
17.95
240
464
190.45
353.14
294.28
18.34
250
482
194.08
366.53
305.44
18.73
RRTD INPUTS
RRTD 1
MESSAGE
RRTD 2
↓
MESSAGE
RRTD 12
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...