GE Multilin
T60 Transformer Protection System
B-23
APPENDIX B
B.4 MEMORY MAPPING
B
30BA
...Repeated for Fault Report 2
Modbus File Transfer (Read/Write)
3100
Name of file to read
---
---
---
F204
(none)
Modbus File Transfer Values (Read Only)
3200
Character position of current block within file
0 to 4294967295
---
1
F003
0
3202
Size of currently-available data block
0 to 65535
---
1
F001
0
3203
Block of data from requested file (122 items)
0 to 65535
---
1
F001
0
Security (Read/Write Setting)
3280
Administrator Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
328A
Administrator Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Security (Read/Write)
328B
Administrator Alphanumeric Password Entry
---
---
---
F202
(none)
Security (Read/Write Setting)
3295
Supervisor Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
329F
Supervisor Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Security (Read/Write)
32A0
Supervisor Alphanumeric Password Entry
---
---
---
F202
(none)
Security (Read/Write Setting)
32AA
Engineer Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
32B4
Engineer Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Security (Read/Write)
32B5
Engineer Alphanumeric Password Entry
---
---
---
F202
(none)
Security (Read/Write Setting)
32BF
Operator Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
32C9
Operator Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Security (Read/Write)
32CA
Operator Alphanumeric Password Entry
---
---
---
F202
(none)
Security (Read/Write Setting)
32D4
Observer Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
32DE
Observer Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Security (Read/Write)
32DF
Observer Alphanumeric Password Entry
---
---
1
F202
(none)
Security (Read Only)
32E9
Reserved for password settings of future roles (63 items)
0 to 65535
---
1
F001
0
3328
Security Status Indicator
0 to 65535
---
1
F618
0
Security (Read/Write Setting)
3329
Session Lockout
0 to 99
---
1
F001
3
332A
Session Lockout Period
0 to 9999
min
1
F001
3
332B
Load Factory Defaults
0 to 1
---
1
F126
0 (No)
332C
Syslog Server IP Address
0 to 4294967295
---
1
F003
0
332E
Syslog Server Port Number
1 to 65535
---
1
F001
514
Security Supervisory (Read/Write Setting)
3331
Device Authentication Enable
0 to 1
---
1
F126
1 (Yes)
3332
Supervisor Role Enable
0 to 1
---
1
F102
0 (Disabled)
3333
Lock Relay
0 to 1
---
1
F102
0 (Disabled)
3334
Factory Service Mode Enable
0 to 1
---
1
F102
0 (Disabled)
3335
Failed Authentication Alarm Enable
0 to 1
---
1
F102
1 (Enabled)
3336
Firmware Lock Alarm
0 to 1
---
1
F102
1 (Enabled)
3337
Settings Lock Alarm
0 to 1
---
1
F102
1 (Enabled)
Table B–10: MODBUS MEMORY MAP (Sheet 15 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...