GE Multilin
T60 Transformer Protection System
B-87
APPENDIX B
B.4 MEMORY MAPPING
B
F126
ENUMERATION: NO/YES CHOICE
0 = No, 1 = Yes
F127
ENUMERATION: LATCHED OR SELF-RESETTING
0 = Latched, 1 = Self-Reset
F128
ENUMERATION: CONTACT INPUT THRESHOLD
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
F129
ENUMERATION: FLEXLOGIC TIMER TYPE
0 = millisecond, 1 = second, 2 = minute
F131
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
F132
ENUMERATION: DEMAND INTERVAL
0 = 5 min, 1 = 10 min, 2 = 15 min, 3 = 20 min, 4 = 30 min,
5 = 60 min
F133
ENUMERATION: PROGRAM STATE
0 = Not Programmed, 1 = Programmed
F134
ENUMERATION: PASS/FAIL
0 = Fail, 1 = OK, 2 = n/a
F137
ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON
FUNCTION
0 = Disabled, 1 = Self-Reset, 2 = Latched
F139
ENUMERATION: DEMAND CALCULATIONS
0 = Thermal Exponential, 1 = Block Interval, 2 = Rolling Demand
F141
ENUMERATION: SELF TEST ERRORS
932
Disconnect switch 13
933
Disconnect switch 14
934
Disconnect switch 15
935
Disconnect switch 16
936
Disconnect switch 17
937
Disconnect switch 18
938
Disconnect switch 19
939
Disconnect switch 20
940
Disconnect switch 21
941
Disconnect switch 22
942
Disconnect switch 23
943
Disconnect switch 24
968
Breaker 1
969
Breaker 2
970
Breaker 3
971
Breaker 4
980
Breaker restrike 1
981
Breaker restrike 2
982
Breaker restrike 3
991
Remote RTD Input 1
992
Remote RTD Input 2
993
Remote RTD Input 3
994
Remote RTD Input 4
995
Remote RTD Input 5
996
Remote RTD Input 6
997
Remote RTD Input 7
998
Remote RTD Input 8
999
Remote RTD Input 9
1000
Remote RTD Input 10
1001
Remote RTD Input 11
1002
Remote RTD Input 12
1012
Thermal overload protection 1
1013
Thermal overload protection 2
Bitmask
Element
Bitmask
Error
0
Any Self Tests
1
IRIG-B Failure
2
Port 1 Offline
3
Port 2 Offline
4
Port 3 Offline
5
Port 4 Offline
6
Port 5 Offline
7
Port 6 Offline
8
RRTD Communications Failure
9
Voltage Monitor
10
FlexLogic Error Token
11
Equipment Mismatch
12
Process Bus Failure
13
Unit Not Programmed
14
System Exception
15
Latching Output Discrepancy
17
Maintenance Alert 01
18
SNTP Failure
19
Maintenance Alert
20
Maintenance Alert
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...