5-290
T60 Transformer Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and
solid-state contact with voltage monitoring.
5.7.10 DIGITAL COUNTERS
PATH: SETTINGS
CONTROL ELEMENTS
DIGITAL COUNTERS
COUNTER 1(8)
There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions from
Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an
external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.
•
COUNTER 1 UNITS:
Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted.
The units label will appear in the corresponding actual values status.
•
COUNTER 1 PRESET:
Sets the count to a required preset value before counting operations begin, as in the case
where a substitute relay is to be installed in place of an in-service relay, or while the counter is running.
•
COUNTER 1 COMPARE:
Sets the value to which the accumulated count value is compared. Three FlexLogic output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the set
value.
•
COUNTER 1 UP:
Selects the FlexLogic operand for incrementing the counter. If an enabled UP input is received when
the accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,648.
•
COUNTER 1 DOWN:
Selects the FlexLogic operand for decrementing the counter. If an enabled DOWN input is
received when the accumulated value is at the limit of –2,147,483,648 counts, the counter will rollover to
+2,147,483,647.
•
COUNTER 1 BLOCK:
Selects the FlexLogic operand for blocking the counting operation. All counter operands are
blocked.
COUNTER 1
COUNTER 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
COUNTER 1 NAME:
Counter 1
Range: 12 alphanumeric
characters
MESSAGE
COUNTER 1 UNITS:
Range: 6 alphanumeric characters
MESSAGE
COUNTER 1 PRESET:
0
Range: –2,147,483,648 to +2,147,483,647
MESSAGE
COUNTER 1 COMPARE:
0
Range: –2,147,483,648 to +2,147,483,647
MESSAGE
COUNTER 1 UP:
Off
Range: FlexLogic operand
MESSAGE
COUNTER 1 DOWN:
Off
Range: FlexLogic operand
MESSAGE
COUNTER 1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
CNT1 SET TO PRESET:
Off
Range: FlexLogic operand
MESSAGE
COUNTER 1 RESET:
Off
Range: FlexLogic operand
MESSAGE
COUNT1 FREEZE/RESET:
Off
Range: FlexLogic operand
MESSAGE
COUNT1 FREEZE/COUNT:
Off
Range: FlexLogic operand
NOTE
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...