2-22
T60 Transformer Protection System
GE Multilin
2.4 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4SPECIFICATIONS
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
2.4.1 PROTECTION ELEMENTS
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
power system devices via communications or different output contacts. If not specified, the operate times given
here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
PERCENT DIFFERENTIAL
Characteristic:
Dual slope percent differential
Minimum pickup:
0.05 to 1.00 pu in steps of 0.001
Slope 1 range:
15 to 100% in steps of 1%
Slope 2 range:
50 to 100% in steps of 1%
Kneepoint 1:
1.0 to 2.0 pu in steps of 0.001
Kneepoint 2:
2.0 to 30.0 pu in steps of 0.001
2
nd
harmonic inhibit level: 1.0 to 40.0% in steps of 0.1
2
nd
harmonic inhibit function: Adaptive, Traditional, Disabled
2
nd
harmonic inhibit mode: Per-phase, 2-out-of-3, Average
5
th
harmonic inhibit range: 1.0 to 40.0% in steps of 0.1
Operate times:
Harmonic inhibits selected: 20 to 30 ms at 60 Hz;
20 to 35 ms at 50 Hz
No harmonic inhibits selected: 5 to 20 ms
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading or ±1% of rated
(whichever is greater) for two windings
setup
INSTANTANEOUS DIFFERENTIAL
Pickup level:
2.00 to 30.00 pu in steps of 0.01
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading or ±1% of rated
(whichever is greater) for two windings
setup
Operate time:
<
20 ms at 3
×
pickup at 60 Hz
PHASE DISTANCE
Characteristic:
mho (memory polarized or offset) or
quad (memory polarized or non-direc-
tional), selectable individually per zone
Number of zones:
5
Directionality:forward, reverse, or non-
directional per zone
Reach (secondary
Ω
):
0.02 to 500.00
Ω
in steps of 0.01
Reach accuracy:
Zone 1:
±5% including the effect of CVT tran-
sients up to an SIR of 30 and ±7% for
30<SIR< 60 at RCA angle
Zones 2 to 5:
±5% for steady fault conditions
Distance:
Characteristic angle:
30 to 90° in steps of 1
Comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
30 to 90° in steps of 1
Limit angle:
30 to 90° in steps of 1
Right blinder (Quad only):
Reach:
0.02 to 500
Ω
in steps of 0.01
Characteristic angle:
60 to 90° in steps of 1
Left Blinder (Quad only):
Reach:
0.02 to 500
Ω
in steps of 0.01
Characteristic angle:
60 to 90° in steps of 1
Time delay:
0.000 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Current supervision:
Level:
line-to-line current
Pickup:
0.050 to 30.000 pu in steps of 0.001
Dropout:
97 to 98%
Memory duration:
5 to 25 cycles in steps of 1
VT location:
all delta-wye and wye-delta transformers
CT location:
all delta-wye and wye-delta transformers
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
Operation time:
1 to 1.5 cycles (typical)
Reset time:
1 power cycle (typical)
NOTE
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...