GE Multilin
T60 Transformer Protection System
B-19
APPENDIX B
B.4 MEMORY MAPPING
B
2197
Breaker Flashover 1 Side 1 Source
0 to 5
---
1
F167
0 (SRC 1)
2198
Breaker Flashover 1 Side 2 Source
0 to 6
---
1
F211
0 (None)
2199
Breaker Flashover 1 Status Closed A
0 to 4294967295
---
1
F300
0
219B
Breaker Flashover 1 Status Closed B
0 to 4294967295
---
1
F300
0
219D
Breaker Flashover 1 Status Closed C
0 to 4294967295
---
1
F300
0
219F
Breaker Flashover 1 Voltage Pickup Level
0 to 1.5
pu
0.001
F001
850
21A0
Breaker Flashover 1 Voltage Difference Pickup Level
0 to 100000
V
1
F060
1000
21A2
Breaker Flashover 1 Current Pickup Level
0 to 1.5
pu
0.001
F001
600
21A3
Breaker Flashover 1 Pickup Delay
0 to 65.535
s
0.001
F001
100
21A4
Breaker Flashover 1 Supervision Phase A
0 to 4294967295
---
1
F300
0
21A6
Breaker Flashover 1 Supervision Phase B
0 to 4294967295
---
1
F300
0
21A8
Breaker Flashover 1 Supervision Phase C
0 to 4294967295
---
1
F300
0
21AA
Breaker Flashover 1 Block
0 to 4294967295
---
1
F300
0
21AC
Breaker Flashover 1 Events
0 to 1
---
1
F102
0 (Disabled)
21AD
Breaker Flashover 1 Target
0 to 2
---
1
F109
0 (Self-Reset)
21AE
Reserved (4 items)
---
---
---
F001
0
21B2
...Repeated for Breaker Flashover 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E0
Breaker 1 Arcing Current Phase A
0 to 99999999
kA
2
-cyc
1
F060
0
21E2
Breaker 1 Arcing Current Phase B
0 to 99999999
kA
2
-cyc
1
F060
0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E4
Breaker 1 Arcing Current Phase C
0 to 99999999
kA
2
-cyc
1
F060
0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E6
Breaker 1 Operating Time Phase A
0 to 65535
ms
1
F001
0
21E7
Breaker 1 Operating Time Phase B
0 to 65535
ms
1
F001
0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E8
Breaker 1 Operating Time Phase C
0 to 65535
ms
1
F001
0
21E9
Breaker 1 Operating Time
0 to 65535
ms
1
F001
0
21EA
...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21EE
...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21F0
...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21F2
...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21FA
...Repeated for module number 3
21FE
...Repeated for module number 4
Breaker Arcing Current Commands (Read/Write Command) (4 modules)
2224
Breaker 1 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
2225
Breaker 2 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
2226
Breaker 3 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
2227
Breaker 4 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
0 to 1
---
1
F126
0 (No)
Transformer Differential and Restraint (Read Only)
2300
Transformer Reference Winding
1 to 6
---
1
F001
1
2301
Transformer Differential Phasor Iad Magnitude
0 to 30
pu
0.001
F001
0
2302
Transformer Differential Phasor Iad Angle
-359.9 to 0
degrees
0.1
F002
0
2303
Transformer Restraint Phasor Iar Magnitude
0 to 30
pu
0.001
F001
0
2304
Transformer Restraint Phasor Iar Angle
-359.9 to 0
degrees
0.1
F002
0
2305
Transformer Differential 2nd Harm Iad Magnitude
0 to 999.9
% fo
0.1
F001
0
2306
Transformer Differential 2nd Harm Iad Angle
-359.9 to 0
degrees
0.1
F002
0
2307
Transformer Differential 5th Harm Iad Magnitude
0 to 999.9
% fo
0.1
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 11 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...