5-118
T60 Transformer Protection System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
3.
Configure source
n
(source 2 for this example) as the current from CTY in Winding 1 in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE 1(4)
settings menu.
SOURCE 2 NAME:
“WDG 1Y”
SOURCE 2 PHASE CT:
“F5”
SOURCE 2 GROUND CT:
“None”
SOURCE 2 PHASE VT:
“None”
SOURCE 2 AUX VT:
“None”
4.
Configure source
n
(source 3 for this example) to be used as the current in Winding 2 in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE 1(4)
settings menu.
SOURCE 3 NAME:
“WDG 2"
SOURCE 3 PHASE CT:
“M1”
SOURCE 3 GROUND CT:
“M1”
SOURCE 3 PHASE VT
: “None”
SOURCE 3 AUX VT:
“None”
5.
Configure the source setting of the transformer windings in the
SYSTEM SETUP
TRANSFORMER
WINDING n
set-
tings menu.
WINDING 1 SOURCE:
“WDG 1X”
WINDING 2 SOURCE:
“WDG 1Y”
WINDING 3 SOURCE:
“WDG 2"
SETUP METHOD B (ALTERNATE)
This approach adds the current from each phase of the CT1 and CT2 together to represent the total winding 1 current. The
procedure is shown below.
1.
Enter the settings for each set of CTs in the
SYSTEM SETUP
AC INPUTS
CURRENT BANK
settings menu, as shown for
Method A above.
2.
Configure Source
n
(Source 1 for this example) to be used as the summed current in Winding 1 in the
SYSTEM SETUP
SIGNAL SOURCES
SOURCE n
settings menu.
SOURCE 1 NAME:
“WDG 1"
SOURCE 1 PHASE CT:
“F1 + F5”
SOURCE 1 GROUND CT:
“None”
SOURCE 1 PHASE VT:
“None”
SOURCE 1 AUX VT:
“None”
3.
Configure Source
n
(Source 2 for this example) to be used as the Winding 2 current in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE n
settings menu.
SOURCE 2 NAME:
“WDG 2"
SOURCE 2 PHASE CT:
“M1”
SOURCE 2 GROUND CT:
“M1”
SOURCE 2 PHASE VT:
“None”
SOURCE 2 AUX VT:
“None”
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...