B-26
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
3742
Authentication Retries
0 to 9999
---
1
F001
3
3743
RADIUS Authentication Shared Secret
---
---
---
F202
(none)
PTP Basic Configuration (Read/Write Setting)
3750
PTP Strict Power Profile
0 to 1
---
1
F102
0 (Disabled)
3751
PTP Domain Number
0 to 255
---
1
F001
0
3752
PTP VLAN Priority
0 to 7
---
1
F001
4
3753
PTP VLAN ID
0 to 4095
---
1
F001
0
3754
Undefined (2 items)
0 to 1
---
1
F001
0
PTP Port Configuration (Read/Write Setting) (3 modules)
3756
PTP Port 1 Function
0 to 1
---
1
F102
0 (Disabled)
3757
PTP Port 1 Path Delay Adder
0 to 60000
ns
1
F001
0
3758
PTP Port 1 Path Delay Asymmetry
-1000 to 1000
ns
1
F002
0
3759
...Repeated for PTP Port 2
375C
...Repeated for PTP Port 3
Real Time Clock Synchronizing Actual Values (Read Only)
375F
RTC Sync Source
0 to 5
---
1
F624
0 (None)
3760
PTP GrandMaster ID
0 to 100
--
1
F073
0
3764
Real Time Clock Accuracy
0 to 999999999
ns
1
F003
0
3766
PTP Port 1 State (3 items)
0 to 4
--
1
F625
0 (Disabled)
3769
RTC Offset
0 to 999999999
ns
1
F004
0
376B
PTP - IRIG-B Delta
-500000000 to 500000000
ns
1
F004
0
Real Time Clock Synchronizing FlexAnalogs (Read Only)
376D
PTP - IRIG-B Delta FlexAnalog
-262143 to 262143
---
1
F004
0
Field Units (Read/Write Setting) (8 modules)
3800
Field Unit 1 ID
0 to 1
---
1
F205
"U1"
3806
Field Unit 1 Function
0 to 1
---
1
F102
0 (Disabled)
3807
Field Unit 1 Type
0 to 3
---
1
F243
0 (CC-05)
3808
Field Unit 1 Serial Number
1 to1
---
1
F205
"000000000000"
380E
Field Unit 1 Port
1 to 4
---
1
F001
1
380F
...Repeated for Field Unit 2
381E
...Repeated for Filed Unit 3
382D
...Repeated for Filed Unit 4
383C
...Repeated for Filed Unit 5
384B
...Repeated for Filed Unit 6
385A
...Repeated for Filed Unit 7
3869
...Repeated for Filed Unit 8
Field Unit Process Card Ports (Read/Write Setting)
3878
Field Unit 1 Process Card Port
0 to 7
---
1
F244
6 (H1a)
3879
Field Unit 2 Process Card Port
0 to 7
---
1
F244
4 (H2a)
387A
Field Unit3 Process Card Port
0 to 7
---
1
F244
2 (H3a)
387B
Field Unit 4 Process Card Port
0 to 7
---
1
F244
0 (H4a)
387C
Field Unit 5 Process Card Port
0 to 7
---
1
F244
7 (H1b)
387D
Field Unit 6 Process Card Port
0 to 7
---
1
F244
5 (H2b)
387E
Field Unit 7 Process Card Port
0 to 7
---
1
F244
3 (H3b)
387F
Field Unit 8 Process Card Port
0 to 7
---
1
F244
1 (H4b)
Field Unit CT VT Settings (Read/Write Setting) (6 modules)
3890
Remote Phase CT x Origin 1
0 to 16
---
1
F247
0 (None)
3891
Remote Phase CT x Origin 2
0 to 16
---
1
F247
0 (None)
3892
Remote Ground CT x Origin 1
0 to 16
---
1
F248
0 (None)
3893
Remote Ground CT x Origin 2
0 to 16
---
1
F248
0 (None)
3894
AC Bank Redundancy Type
0 to 2
---
1
F261
1 (Dependability
Biased)
3895
Remote Phase CT 1 Primary
1 to 65000
---
1
F001
1
3896
Remote Phase CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
Table B–10: MODBUS MEMORY MAP (Sheet 18 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...