5-18
T60 Transformer Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Security Alarm Settings
CYBERSENTRY SETTINGS THROUGH THE FRONT PANEL
PATH: SETTINGS
PRODUCT SETUP
SECURITY
LOGIN
: This setting is applicable for
Device Authentication
only. This setting allows a user to login with a specific role, see
descriptions below. For the Supervisor role, the “Supervisor Role” setting should be enabled.
Whenever a new role is logged in, the user is prompted with a display to enter a password. Passwords must obey the
requirements specified at the beginning of the chapter in the Password Requirements section.The UR device supports five
roles. All roles have their corresponding passwords. The Observer role is the only role that does not require a password.
The roles are defined as follows:
•
Administrator: Complete read and write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
•
Engineer: Complete read and write access to all settings and commands with the exception of configuring Security set-
tings and Firmware upgrades. This role does not allow concurrent access.
•
Operator: The Operator has read/write access to all settings under the command menu/section. This role does not
exist offline.
•
Supervisor: This is only an approving role. This role’s authentication commits setting changes submitted by Administra-
tor or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not approve changes
after the fact. Only Supervisor can set the Settings and Firmware Lock in the Security Settings. This role also has the
ability to forcefully logoff any other role and clear the security event log. This role can also be disabled, but only
through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role.
SETTING NAME
DESCRIPTION / DETAILS
MIN
MAX
DEFAULT UNITS
MINIMUM
PERMISSIONS
Failed
Authentications
A threshold number indicating when an alarm is
set off to indicate too many failed authentication
attempts
0
(disabled)
99
3
-
Administrator
Firmware lock
A Boolean value indicating if the device can
receive a firmware upgrade. If Yes and a
firmware upgrade attempt is made, the device
alarm activates. If No the device alarm does not
activate. On each firmware upgrade this setting
goes back to the default.
No
Yes
Yes
-
Administrator
Settings lock
A Boolean value indicating if the device can
accept any settings changes. If Yes and a
settings change attempt is made, the device
alarm activates. If No, the device alarm does not
activate.
No
Yes
Yes
-
Supervisor
(Administrator if
Supervisor has
been disabled)
SECURITY
LOGIN:
None
Range: Administrator, Engineer, Supervisor,
Operator, Factory (for factory use only), None
MESSAGE
CHANGE LOCAL
PASSWORDS
See below
MESSAGE
SESSION
SETTINGS
MESSAGE
RESTORE DEFAULTS
MESSAGE
SUPERVISORY
MESSAGE
SYSLOG IP ADDRESS:
0.0.0.0
Range: 0.0.0.0, 255.255.255.255
MESSAGE
SYSLOG PORT NUMBER:
514
Range: 1 to 65535
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...