B.4 MEMORY MAPPING
APPENDIX B
B
C3F0
...Repeated for Virtual Output 89
C3F8
...Repeated for Virtual Output 90
C400
...Repeated for Virtual Output 91
C408
...Repeated for Virtual Output 92
C410
...Repeated for Virtual Output 93
C418
...Repeated for Virtual Output 94
C420
...Repeated for Virtual Output 95
C428
...Repeated for Virtual Output 96
Mandatory (Read/Write Setting or Command)
C430
Test Mode Function
0 to 2
---
1
F245
0 (Disabled)
C431
Force VFD and LED
0 to 1
---
1
F126
0 (No)
C432
Test Mode Initiate
0 to 4294967295
---
1
F300
1
Clear Commands (Read/Write)
C434
Clear All Relay Records Command
0 to 1
---
1
F126
0 (No)
Mandatory (Read Only)
C435
DSP Advanced Diagnostics Active
0 to 1
--
1
F126
0 (No)
C436
Synchrophasor Feature Active
0 to 1
--
1
F126
0 (No)
Mandatory (Read/Write Command)
C437
Relay Reboot Command
0 to 1
---
1
F126
0 (No)
C438
Save Volatile Data
0 to 1
---
1
F126
0 (No)
Clear Records (Read/Write Setting)
C446
Clear Demand Operand
0 to 4294967295
---
1
F300
0
C452
Clear User Fault Reports Operand
0 to 4294967295
---
1
F300
0
C454
Clear Event Records Operand
0 to 4294967295
---
1
F300
0
C456
Clear Oscillography Operand
0 to 4294967295
---
1
F300
0
C458
Clear Data Logger Operand
0 to 4294967295
---
1
F300
0
C45A
Clear Breaker 1 Arcing Current Operand
0 to 4294967295
---
1
F300
0
C45C
Clear Breaker 2 Arcing Current Operand
0 to 4294967295
---
1
F300
0
C45E
Clear Breaker 3 Arcing Current Operand
0 to 4294967295
---
1
F300
0
C460
Clear Breaker 4 Arcing Current Operand
0 to 4294967295
---
1
F300
0
C468
Clear Energy Operand
0 to 4294967295
---
1
F300
0
C46C
Clear Unauthorized Access Operand
0 to 4294967295
---
1
F300
0
C470
Clear Platform Direct Input/Output Statistics Operand
0 to 4294967295
---
1
F300
0
C472
Reserved (13 items)
---
---
---
F001
0
Platform Direct Outputs (Read/Write Setting) (32 modules)
C600
Direct Output 1 Operand
0 to 4294967295
---
1
F300
0
C602
Direct Output 1 Events
0 to 1
---
1
F102
0 (Disabled)
C603
...Repeated for Direct Output 2
C606
...Repeated for Direct Output 3
C609
...Repeated for Direct Output 4
C60C
...Repeated for Direct Output 5
C60F
...Repeated for Direct Output 6
C612
...Repeated for Direct Output 7
C615
...Repeated for Direct Output 8
C618
...Repeated for Direct Output 9
C61B
...Repeated for Direct Output 10
C61E
...Repeated for Direct Output 11
C621
...Repeated for Direct Output 12
C624
...Repeated for Direct Output 13
C627
...Repeated for Direct Output 14
C62A
...Repeated for Direct Output 15
C62D
...Repeated for Direct Output 16
C630
...Repeated for Direct Output 17
C633
...Repeated for Direct Output 18
Table B–10: MODBUS MEMORY MAP (Sheet 62 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...