5-262
T60 Transformer Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
d) NEUTRAL OVERVOLTAGE
(ANSI 59N, IEC PTOV)
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
VOLTAGE ELEMENTS
NEUTRAL OV1(3)
There are three neutral overvoltage elements available. The neutral overvoltage element can be used to detect asymmetri-
cal system voltage condition due to a ground fault or to the loss of one or two phases of the source. The element responds
to the system neutral voltage (3V_0), calculated from the phase voltages. The nominal secondary voltage of the phase volt-
age channels entered under
SETTINGS
SYSTEM SETUP
AC INPUTS
VOLTAGE BANK
PHASE VT SECONDARY
is the
p.u. base used when setting the pickup level.
The neutral overvoltage element can provide a time-delayed operating characteristic versus the applied voltage (initialized
from FlexCurves A, B, or C) or be used as a definite time element. The
NEUTRAL OV1 PICKUP DELAY
setting applies only if
the
NEUTRAL OV1 CURVE
setting is “Definite time”. The source assigned to this element must be configured for a phase VT.
VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to
be wye-connected.
Figure 5–127: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC
NEUTRAL OV1
NEUTRAL OV1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
NEUTRAL OV1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
NEUTRAL OV1 PICKUP:
0.300 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
NEUTRAL OV1 CURVE:
Definite time
Range: Definite time, FlexCurve A, FlexCurve B,
FlexCurve C
MESSAGE
NEUTRAL OV1 PICKUP:
DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
NEUTRAL OV1 RESET:
DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
NEUTRAL OV1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
NEUTRAL OV1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
NEUTRAL OV1 EVENTS:
Disabled
Range: Disabled, Enabled
827848A3.CDR
FLEXLOGIC OPERANDS
NEUTRAL OV1
FUNCTION:
NEUTRAL OV1 BLOCK:
NEUTRAL OV1 SIGNAL
SOURCE:
NEUTRAL OV1 PICKUP:
NEUTRAL OV1 DPO
NEUTRAL OV1 OP
NEUTRAL OV1 PKP
RUN
AND
SETTING
SETTING
NEUTRAL OV1 RESET
DELAY :
NEUTRAL OV1 PICKUP
DELAY :
SETTING
Enabled=1
t
PKP
t
RST
SETTING
SETTING
Off=0
ZERO SEQ VOLT (V_0)
3V_0 Pickup
<
NEUTRAL OV1 CURVE :
t
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...