5-202
T60 Transformer Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
The power swing detect element provides both power swing blocking and out-of-step tripping functions. The element mea-
sures the positive-sequence apparent impedance and traces its locus with respect to either two or three user-selectable
operating characteristic boundaries. Upon detecting appropriate timing relations, the blocking and tripping indications are
given through FlexLogic operands. The element incorporates an adaptive disturbance detector. This function does not trig-
ger on power swings, but is capable of detecting faster disturbances – faults in particular – that may occur during power
swings. Operation of this dedicated disturbance detector is signaled via the
POWER SWING 50DD
operand.
MESSAGE
POWER SWING OUTER
LIMIT ANGLE: 120°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING MIDDLE
LIMIT ANGLE: 90°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING INNER
LIMIT ANGLE: 60°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING OUTER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING OUTER
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING MIDDLE
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING MIDDLE
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING INNER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING INNER
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING PICKUP
DELAY 1: 0.030 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
POWER SWING RESET
DELAY 1: 0.050 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
POWER SWING PICKUP
DELAY 2: 0.017 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
POWER SWING PICKUP
DELAY 3: 0.009 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
POWER SWING PICKUP
DELAY 4: 0.017 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
POWER SWING SEAL-IN
DELAY: 0.400 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
POWER SWING TRIP
MODE: Delayed
Range: Early, Delayed
MESSAGE
POWER SWING BLK:
Off
Range: Flexlogic operand
MESSAGE
POWER SWING
TARGET: Self-Reset
Range: Self-Reset, Latched, Disabled
MESSAGE
POWER SWING
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...