B-48
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
77FF
Ohm Inputs 1 Reserved (9 items)
0 to 65535
---
1
F001
0
7808
...Repeated for Ohm Inputs 2
Phasor Measurement Unit Recorder Config Counter Command (Read/Write Command)
781A
PMU 1 Recorder Clear Config Counter
0 to 1
---
1
F126
0 (No)
Phasor Measurement Unit One-shot Command (Read/Write Setting)
788C
PMU One-shot Function
0 to 1
---
1
F102
0 (Disabled)
788D
PMU One-shot Sequence Number
0 to 99
---
1
F001
1
788E
PMU One-shot Time
0 to 235959
---
1
F050
0
Phasor Measurement Unit Recording Values (Read Only)
7890
PMU 1 Available Records
0 to 65535
---
1
F001
0
7891
PMU 1 Second Per Record
0 to 6553.5
---
0.1
F003
0
7893
PMU 1 Last Cleared Date
0 to 400000000
---
1
F050
0
Phasor Measurement Unit Test Values (Read/Write Setting)
78AE
PMU 1 Test Function
0 to 1
---
1
F102
0 (Disabled)
78AF
PMU 1 Phase A Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
78B1
PMU 1 Page A Voltage Test Angle
-180 to 180
°
0.05
F002
0
78B2
PMU 1 Phase B Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
78B4
PMU 1 Phase B Voltage Test Angle
-180 to 180
°
0.05
F002
-12000
78B5
PMU 1 Phase C Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
78B7
PMU 1 Phase C Voltage Test Angle
-180 to 180
°
0.05
F002
12000
78B8
PMU 1 Auxiliary Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
78BA
PMU 1 Auxiliary Voltage Test Angle
-180 to 180
°
0.05
F002
0
78BB
PMU 1 Phase A Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
78BD
PMU 1 Phase A Current Test Angle
-180 to 180
°
0.05
F002
-1000
78BE
PMU 1 Phase B Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
78C0
PMU 1 Phase B Current Test Angle
-180 to 180
°
0.05
F002
-13000
78C1
PMU 1 Phase C Current Test Magnitude
0 to 9.999
kA
0.001
F003
1000
78C3
PMU 1 Phase C Current Test Angle
-180 to 180
°
0.05
F002
11000
78C4
PMU 1 Ground Current Test Magnitude
0 to 9.999
kA
0.001
F004
0
78C6
PMU 1 Ground Current Test Angle
-180 to 180
°
0.05
F002
0
78C7
PMU 1 Test Frequency
20 to 70
Hz
0.001
F003
60000
78C9
PMU 1 Test df/dt
-10 to 10
Hz/s
0.01
F002
0
Underfrequency (Read/Write Setting) (6 modules)
7A80
Underfrequency 1 Function
0 to 1
---
1
F102
0 (Disabled)
7A81
Underfrequency 1 Block
0 to 4294967295
---
1
F300
0
7A83
Underfrequency 1 Min Current
0.1 to 1.25
pu
0.01
F001
10
7A84
Underfrequency 1 Pickup
20 to 65
Hz
0.01
F001
5950
7A85
Underfrequency 1 Pickup Delay
0 to 65.535
s
0.001
F001
2000
7A86
Underfrequency 1 Reset Delay
0 to 65.535
s
0.001
F001
2000
7A87
Underfrequency 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7A88
Underfrequency 1 Events
0 to 1
---
1
F102
0 (Disabled)
7A89
Underfrequency 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7A8A
Underfrequency 1 Reserved (5 items)
0 to 1
---
1
F001
0
7A8F
...Repeated for Underfrequency 2
7A9E
...Repeated for Underfrequency 3
7AAD
...Repeated for Underfrequency 4
7ABC
...Repeated for Underfrequency 5
7ACB
...Repeated for Underfrequency 6
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60
User Programmable Pushbutton 1 Function
0 to 2
---
1
F137
0 (Disabled)
7B61
User Programmable Pushbutton 1 Top Line
---
---
---
F202
(none)
7B6B
User Programmable Pushbutton 1 On Text
---
---
---
F202
(none)
7B75
User Programmable Pushbutton 1 Off Text
---
---
---
F202
(none)
7B7F
User Programmable Pushbutton 1 Drop-Out Time
0 to 60
s
0.05
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 40 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...