GE Multilin
T60 Transformer Protection System
B-57
APPENDIX B
B.4 MEMORY MAPPING
B
Breaker Restrike (Read/Write Setting) (3 modules)
9930
Breaker Restrike 1 Function
0 to 1
---
1
F102
0 (Disabled)
9931
Breaker Restrike 1 Block
0 to 4294967295
---
1
F300
0
9933
Breaker Restrike 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
9934
Breaker Restrike 1 Pickup
0.10 to 2.00
pu
0.01
F001
50
9935
Breaker Restrike 1 Reset Delay
0 to 65.535
s
0.001
F001
100
9936
Breaker Restrike 1 HF Detect
0 to 1
---
1
F102
1 (Enabled)
9937
Breaker Restrike 1 Breaker Open
0 to 4294967295
---
1
F300
0
9939
Breaker Restrike 1 Open Command
0 to 4294967295
---
1
F300
0
993B
Breaker Restrike 1 Close Command
0 to 4294967295
---
1
F300
0
993D
Breaker Restrike 1 Target
0 to 2
---
1
F109
0 (Self-reset)
993E
Breaker Restrike 1 Events
0 to 1
---
1
F102
0 (Disabled)
993F
Reserved (2 items)
---
---
---
F002
0
9941
...Repeated for Breaker Restrike 2
9952
...Repeated for Breaker Restrike 3
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9980
Teleprotection Clear Lost Packets
0 to 1
---
1
F126
0 (No)
Teleprotection Inputs/Outputs (Read/Write Settings)
9990
Teleprotection Function
0 to 1
---
1
F102
0 (Disabled)
9991
Teleprotection Number of Terminals
2 to 3
---
1
F001
2
9992
Teleprotection Number of Channels
1 to 2
---
1
F001
1
9993
Teleprotection Local Relay ID
0 to 255
---
1
F001
0
9994
Teleprotection Terminal 1 ID
0 to 255
---
1
F001
0
9995
Teleprotection Terminal 2 ID
0 to 255
---
1
F001
0
9996
Reserved (10 items)
0 to 1
---
1
F001
0
9A00
Teleprotection Input 1-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9A10
Teleprotection Input 2-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9A20
Teleprotection Output 1-n Operand (16 items)
0 to 4294967295
---
1
F300
0
9A40
Teleprotection Output 2-n Operand (16 items)
0 to 4294967295
---
1
F300
0
Teleprotection Channel Tests (Read Only)
9AA0
Teleprotection Channel 1 Status
0 to 2
---
1
F134
1 (OK)
9AA1
Teleprotection Channel 1 Number of Lost Packets
0 to 65535
---
1
F001
0
9AA2
Teleprotection Channel 2 Status
0 to 2
---
1
F134
2 (n/a)
9AA3
Teleprotection Channel 2 Number of Lost Packets
0 to 65535
---
1
F001
0
9AA4
Teleprotection Network Status
0 to 2
---
1
F134
2 (n/a)
9AAF
Teleprotection Channel 1 Input States
0 to 1
---
1
F500
0
9AB0
Teleprotection Channel 2 Input States
0 to 1
---
1
F500
0
9AC0
Teleprotection Input 1 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
9AD0
Teleprotection Input 2 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
VT Fuse Failure (Read/Write Setting) (6 modules)
A09A
VT Fuse Failure1 Function
0 to 1
---
1
F102
0 (Disabled)
A09B
VT Fuse Failure Neutral Wire Open1 Function
0 to 1
---
1
F102
0 (Disabled)
A09C
VT Fuse Failure Neutral Wire Open 1 3rd Harmonic Pickup
0 to 3
pu
0.001
F001
100
A09D
...Repeated for module number 2
A0A0
...Repeated for module number 3
A0A3
...Repeated for module number 4
A0A6
...Repeated for module number 5
A0A9
...Repeated for module number 6
VT Fuse Failure Actuals (Read Only) (6 modules)
A0AC
VT Fuse Failure 1 V0 3rd Harmonic
0 to 999999.999
V
0.001
F060
0
A0AE
...Repeated for module number 2
A0B0
...Repeated for module number 3
A0B2
...Repeated for module number 4
A0B4
...Repeated for module number 5
Table B–10: MODBUS MEMORY MAP (Sheet 49 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...