GE Multilin
T60 Transformer Protection System
B-97
APPENDIX B
B.4 MEMORY MAPPING
B
F259
ENUMERATION: BRICK RTD TYPE
0 = 100 Ohm Nickel, 1 = 120 Ohm Nickel, 2 = 100 Ohm Platinum
F260
ENUMERATION: DATA LOGGER MODE
0 = Continuous, 1 = Trigger
F261
ENUMERATION: BANK REDUNDANCY TYPE
0 = None, 1 = Dependability Biased, 2 = Security Biased
F262
ENUMERATION: BRICK STATUS
0 = Disabled, 1 = OK, 2 = Communications Trouble, 3 = Equip-
ment Mismatch, 4 = Brick Trouble
F300
UR_UINT32: FLEXLOGIC BASE TYPE (15-bit type)
The FlexLogic BASE type is 14 bits and is combined with a 17-bit
descriptor and 1 bit for the protection element to form a 32-bit
value. The combined bits are of the form:
PTTTTTTTTTTTTTTDDDDDDDDDDDDDDDDD, where P bit if
set indicates that the FlexLogic type is associated with a protection
element state and D represents bits for the type in F124 format. If
P bit is not set, then the T represents bits for the type and D repre-
sents range.
The values in square brackets indicate the base type with P prefix
[PTTTTTTTTTTTTTT] and the values in round brackets indicate
the descriptor range. The left-most D bit indicates whether the type
is an ON or OFF type. There can be a total 65535 BASE type ele-
ments, 131071 protection element IDs, and 16383 element states.
There can be a total of 65535 descriptors of each type.
[0] Off (0) – This is boolean FALSE value
[1] On (1) – This is boolean TRUE value
[2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
[4] VIRTUAL INPUTS (1 to 32)
[6] VIRTUAL OUTPUTS (1 to 64)
[8] CONTACT OUTPUTS
[10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64)
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64)
[12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64)
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64)
[14] REMOTE INPUTS (1 to 32)
[16] DIRECT INPUTS (1 to 96
[18] REMOTE OUTPUT DNA BIT PAIRS (1 to 32)
[20] REMOTE OUTPUT UserSt BIT PAIRS (1 to 32)
[22] REMOTE DEVICE ONLINE (1 to 16)
[24] MISCELLANEOUS EQUATION
[26] TELEPROTECTION INPUTS
[28] INSERT (via keypad only)
[30] DELETE (via keypad only)
[32] END
[34] NOT (1 INPUT)
[36] 2 INPUT XOR (0)
[38] LATCH SET/RESET (2 inputs)
[40] OR (2 to 16 inputs)
[42] AND (2 to 16 inputs)
[44] NOR (2 to 16 inputs)
[46] NAND (2 to 16 inputs)
[48] TIMER (1 to 32)
[50] ASSIGN VIRTUAL OUTPUT (1 to 64)
[52] ONE SHOT
[54] SELF-TEST ERROR (see F141 for range)
[56] PLATFORM DIRECT INPUT (1 to 96)
[58] PLATFORM DIRECT OUTPUT (1 to 96)
[60] PLATFORM DIRECT DEVICE (1 to 8)
[62] MISCELLANEOUS EVENTS (see F146 for range)
[64] PDC NETWORK CONTROL
[66] PMU RECORDER OUT OF MEMORY
[68] PMU RECORDER STOPPED
[128 to 255] ELEMENT STATES (see the Element States section
in the Modbus memory map)
F400
UR_UINT16: CT/VT BANK SELECTION
F450
UR_UINT16: AMBIENT SENSOR TYPES
This is a dynamic format code that is populated at initialization with
transducer types as specified in the UR order code.
F460
UR_UINT16: TOP-OIL SENSOR TYPES
This is a dynamic format code that is populated at initialization with
transducer types as specified in the UR order code.
F470
UR_UINT16: TRANSFORMER REFERENCE WINDING SELEC-
TION
F491
ENUMERATION: ANALOG INPUT MODE
0 = Default Value, 1 = Last Known
2
U2
3
U3
4
U4
5
U5
6
U6
7
U7
8
U8
Value
Description
Bitmask
Bank selection
0
Card 1 Contact 1 to 4
1
Card 1 Contact 5 to 8
2
Card 2 Contact 1 to 4
3
Card 2 Contact 5 to 8
4
Card 3 Contact 1 to 4
5
Card 3 Contact 5 to 8
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...