GE Multilin
T60 Transformer Protection System
B-31
APPENDIX B
B.4 MEMORY MAPPING
B
4097
Port 1 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
4098
Port 2 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
4099
Port 3 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
409A
DNP Channel 1 Port
0 to 5
---
1
F177
0 (None)
409B
DNP Channel 2 Port
0 to 5
---
1
F177
0 (None)
409C
DNP Address
0 to 65519
---
1
F001
1
409E
DNP Client Addresses (2 items)
0 to 4294967295
---
1
F003
0
40A3
TCP Port Number for the Modbus protocol
0 to 65535
---
1
F001
502
40A4
TCP/UDP Port Number for the DNP Protocol
0 to 65535
---
1
F001
20000
40A5
TCP Port Number for the HTTP (Web Server) Protocol
0 to 65535
---
1
F001
80
40A6
Main UDP Port Number for the TFTP Protocol
0 to 65535
---
1
F001
69
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means “automatic”) (2 items)
0 to 65535
---
1
F001
0
40A9
DNP Unsolicited Responses Function
0 to 1
---
1
F102
0 (Disabled)
40AA
DNP Unsolicited Responses Timeout
0 to 60
s
1
F001
5
40AB
DNP Unsolicited Responses Maximum Retries
1 to 255
---
1
F001
10
40AC
DNP Unsolicited Responses Destination Address
0 to 65519
---
1
F001
1
40AD
Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
40AE
DNP Current Scale Factor
0 to 8
---
1
F194
2 (1)
40AF
DNP Voltage Scale Factor
0 to 8
---
1
F194
2 (1)
40B0
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B1
DNP Energy Scale Factor
0 to 8
---
1
F194
2 (1)
40B2
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B3
DNP Other Scale Factor
0 to 8
---
1
F194
2 (1)
40B4
DNP Current Default Deadband
0 to 100000000
---
1
F003
30000
40B6
DNP Voltage Default Deadband
0 to 100000000
---
1
F003
30000
40B8
DNP Power Default Deadband
0 to 100000000
---
1
F003
30000
40BA
DNP Energy Default Deadband
0 to 100000000
---
1
F003
30000
40BC
DNP Power Factor Default Deadband
0 to 100000000
--
1
F003
30000
40BE
DNP Other Default Deadband
0 to 100000000
---
1
F003
30000
40C0
DNP IIN Time Synchronization Bit Period
1 to 10080
min
1
F001
1440
40C1
DNP Message Fragment Size
30 to 2048
---
1
F001
240
40C2
DNP Client Address 3
0 to 4294967295
---
1
F003
0
40C4
DNP Client Address 4
0 to 4294967295
---
1
F003
0
40C6
DNP Client Address 5
0 to 4294967295
---
1
F003
0
40C8
DNP Number of Paired Binary Output Control Points
0 to 32
---
1
F001
0
40C9
DNP TCP Connection Timeout
10 to 7200
s
1
F001
120
40CA
DNP Communications Reserved (22 items)
0 to 1
---
1
F001
0
40E0
TCP Port Number for the IEC 60870-5-104 Protocol
0 to 65535
---
1
F001
2404
40E1
IEC 60870-5-104 Protocol Function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 Protocol Cyclic Data Transmit Period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 Current Default Threshold
0 to 100000000
---
1
F003
30000
40E6
IEC 60870-5-104 Voltage Default Threshold
0 to 100000000
---
1
F003
30000
40E8
IEC 60870-5-104 Power Default Threshold
0 to 100000000
---
1
F003
30000
40EA
IEC 60870-5-104 Energy Default Threshold
0 to 100000000
---
1
F003
30000
40EC
IEC 60870-5-104 Power Default Threshold
0 to1
---
0.01
F001
100
40EE
IEC 60870-5-104 Other Default Threshold
0 to 100000000
---
1
F003
30000
40F0
IEC 60870-5-104 Client Address (5 items)
0 to 4294967295
---
1
F003
0
4104
IEC 60870-5-104 Redundancy Port Enabled/Disabled
0 to 1
---
1
F126
0 (No)
4105
Port 2 IP Address
0 to 4294967295
---
1
F003
2130706433
4107
Port 2 IP Subnet Mask
0 to 4294967295
---
1
F003
4278190080
4109
Port 2 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
410B
PRT2 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
Table B–10: MODBUS MEMORY MAP (Sheet 23 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...