GE Multilin
T60 Transformer Protection System
B-35
APPENDIX B
B.4 MEMORY MAPPING
B
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (6 modules)
4500
Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
4501
Phase VT 1 Secondary
25 to 240
V
0.1
F001
664
4502
Phase VT 1 Ratio
1 to 24000
:1
1
F060
1
4504
Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
4505
Auxiliary VT 1 Secondary
25 to 240
V
0.1
F001
664
4506
Auxiliary VT 1 Ratio
1 to 24000
:1
1
F060
1
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
4518
...Repeated for VT Bank 4
4520
...Repeated for VT Bank 5
4528
...Repeated for VT Bank 6
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
0 to 1
---
1
F206
“SRC 1"
4583
Source 1 Phase CT
0 to 63
---
1
F400
0
4584
Source 1 Ground CT
0 to 63
---
1
F400
0
4585
Source 1 Phase VT
0 to 63
---
1
F400
0
4586
Source 1 Auxiliary VT
0 to 63
---
1
F400
0
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
4602
Frequency and Phase Reference
0 to 5
---
1
F167
0 (SRC 1)
4603
Frequency Tracking Function
0 to 1
---
1
F102
1 (Enabled)
Transformer General (Read/Write Setting)
4630
Transformer Number of Windings
2 to 6
---
1
F001
2
4631
Transformer Phase Compensation
0 to 1
---
1
F160
0 (Internal
(software))
4632
Transformer Load Loss at Rated Load
1 to 20000
kW
1
F001
100
4633
Transformer Rated Winding Temperature Rise
0 to 4
---
1
F161
1 (65°C (oil))
4634
Transformer No Load Loss
1 to 20000
kW
1
F001
10
4635
Transformer Type of Cooling
0 to 6
---
1
F162
0 (OA)
4636
Transformer Top-oil Rise Over Ambient
1 to 200
°C
1
F001
35
4637
Transformer Thermal Capacity
0 to 200
kWh/°C
0.01
F001
10000
4638
Transformer Winding Thermal Time Constant
0.25 to 15
min
0.01
F001
200
4639
Transformer Reference Winding Manual Selection
0 to 7
---
1
F470
0
(Auto. Selection)
Transformer Windings (Read/Write Settings) (6 modules)
4640
Transformer Winding 1 Source
0 to 5
---
1
F167
0 (SRC 1)
4641
Transformer Winding 1 Rated MVA
0.001 to 2000
MVA
0.001
F003
100000
4643
Transformer Winding 1 Nominal Phase-Phase Voltage
0.001 to 2000
kV
0.001
F003
220000
4645
Transformer Winding 1 Connection
0 to 2
---
1
F163
0 (Wye)
4646
Transformer Winding 1 Grounding
0 to 1
---
1
F164
0 (Not within
zone)
4647
Transformer Winding 1 Angle w.r.t. Winding 1
-359.9 to 0
degrees
0.1
F002
0
4651
Transformer Winding 1 Resistance
0.0001 to 100
ohms
0.0001
F003
100000
4653
...Repeated for Transformer Winding 2
4666
...Repeated for Transformer Winding 3
4679
...Repeated for Transformer Winding 4
468C
...Repeated for Transformer Winding 5
Table B–10: MODBUS MEMORY MAP (Sheet 27 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...