GE Multilin
T60 Transformer Protection System
5-37
5 SETTINGS
5.2 PRODUCT SETUP
5
When a 0 value is involved in a change, the changes to the
MODBUS TCP PORT NUMBER
setting take effect when the
T60 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
i) PROTOCOL
The Protocol menu setting allows selection of one of the following protocols: DNP 3.0, IEC60870-104, or IEC60870-103.
For any change to take effect, restart the unit.
The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on the
RS232, RS485, and Ethernet ports. It shows all possible combinations of the
PROTOCOL
and
DNP CHANNEL 1(2) PORT
set-
tings.
Table 5–6: PORT AND PROTOCOL COMBINATIONS
PROTOCOL
SETTING
DNP CHANNEL 1(2) PORT
SETTINGS
RS232
RS485
ETHERNET
DNP
Channel 1: Eth TCP
Channel 2: Eth TCP
Modbus
Modbus
DNP, Modbus, IEC 61850
Channel 1: Eth TCP
Channel 2: none
Modbus
Modbus
DNP, Modbus, IEC 61850
Channel 1: none
Channel 2: Eth TCP
Modbus
Modbus
DNP, Modbus, IEC 61850
Channel 1: Eth UDP
Channel 2: none
Modbus
Modbus
DNP, Modbus, IEC 61850
Channel 1: Eth TCP
Channel 2: RS485
Modbus
DNP
DNP, Modbus, IEC 61850
Channel 1: Eth TCP
Channel 2: RS232
DNP
Modbus
DNP, Modbus, IEC 61850
Channel 1: Eth UDP
Channel 2: RS485
Modbus
DNP
DNP, Modbus, IEC 61850
Channel 1: Eth UDP
Channel 2: RS232
DNP
Modbus
DNP, Modbus, IEC 61850
Channel 1: RS485
Channel 2: Eth TCP
Modbus
DNP
DNP, Modbus, IEC 61850
Channel 1: RS232
Channel 2: Eth TCP
DNP
Modbus
DNP, Modbus, IEC 61850
Channel 1: RS485
Channel 2: RS232
DNP
DNP
Modbus, IEC 61850
Channel 1: RS232
Channel 2: RS485
DNP
DNP
Modbus, IEC 61850
Channel 1: RS485
Channel 2: none
Modbus
DNP
Modbus, IEC 61850
IEC 104
Modbus
Modbus
IEC 104, Modbus, IEC 61850
IEC 103
Modbus
IEC 103
Modbus, IEC 61850
NOTE
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...