The metered differential current, restraint current, second harmonic current, and fifth harmonic current are displayed for
each phase. Refer to the
Percent differential
section in chapter 5 for details on how these values are calculated.
If differential current in any phase is below the hard-coded cutoff of 0.04 pu, then the differential, 2nd harmonic, and 5th
harmonic currents are forced to zero.
b) THERMAL ELEMENTS
PATH: ACTUAL VALUES
METERING
TRANSFORMER
THERMAL ELEMENTS
DIFFERENTIAL AND
RESTRAINT
REFERENCE WINDING:
Winding 1
MESSAGE
DIFF PHASOR Iad:
0.000 pu
0.0°
MESSAGE
REST PHASOR Iar:
0.000 pu
0.0°
MESSAGE
DIFF 2ND HARM Iad:
0.0% fo
0.0°
MESSAGE
DIFF 5TH HARM Iad:
0.0% fo
0.0°
MESSAGE
DIFF PHASOR Ibd:
0.000 pu
0.0°
MESSAGE
REST PHASOR Ibr:
0.000 pu
0.0°
MESSAGE
DIFF 2ND HARM Ibd:
0.0% fo
0.0°
MESSAGE
DIFF 5TH HARM Ibd:
0.0% fo
0.0°
MESSAGE
DIFF PHASOR Icd:
0.000 pu
0.0°
MESSAGE
REST PHASOR Icr:
0.000 pu
0.0°
MESSAGE
DIFF 2ND HARM Icd:
0.0% fo
0.0°
MESSAGE
DIFF 5TH HARM Icd:
0.0% fo
0.0°
THERMAL
ELEMENTS
TOP OIL °C:
70°C
MESSAGE
HOTTEST-SPOT °C:
130°
MESSAGE
AGING FACTOR:
1.2
MESSAGE
DAILY RATE LOL:
15 hrs
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...