GE Multilin
T60 Transformer Protection System
5-183
5 SETTINGS
5.6 GROUPED ELEMENTS
5
Five zones of phase distance protection with a minimum 150 ms time delay are provided as backup protection for trans-
formers or adjacent lines.
The phase mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, and overcurrent supervising characteristics. When set to “Non-directional”, the mho function becomes an offset
mho with the reverse reach controlled independently from the forward reach, and all the directional characteristics
removed.
The phase quadrilateral distance function is comprised of a reactance characteristic, right and left blinders, and 100%
memory-polarized directional and current supervising characteristics. When set to “Non-directional”, the quadrilateral func-
tion applies a reactance line in the reverse direction instead of the directional comparators. Refer to Chapter 8 for additional
information.
Each phase distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
1.
The
SIGNAL SOURCE
setting (common for the distance elements of all zones as entered under
SETTINGS
GROUPED
ELEMENTS
SETTING GROUP 1(6)
DISTANCE
).
2.
The
MEMORY DURATION
setting (common for the distance elements of all zones as entered under
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
DISTANCE
).
MESSAGE
PHS DIST Z1 REV
REACH: 2.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
PHS DIST Z1 REV
REACH RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1
COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1
DIR RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1
DIR COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1 QUAD
RGT BLD: 10.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
PHS DIST Z1 QUAD
RGT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
PHS DIST Z1 QUAD
LFT BLD: 10.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
PHS DIST Z1 QUAD
LFT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
PHS DIST Z1
SUPV: 0.200 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
PHS DIST Z1 VOLT
LEVEL: 0.000 pu
Range: 0.000 to 5.000 pu in steps of 0.001
MESSAGE
PHS DIST Z1
DELAY: 0.150 s
Range: 0.150 to 65.535 s in steps of 0.001
MESSAGE
PHS DIST Z1 BLK:
Off
Range: FlexLogic operand
MESSAGE
PHS DIST Z1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
PHS DIST Z1
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...