This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient monitor-
ing. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are packed so
that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states which
are of interest to the user are available in a minimum number of Modbus registers.
The state bits may be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommo-
date the 256 state bits.
5.2.16 USER-DEFINABLE DISPLAYS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
USER-DEFINABLE DISPLAYS
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing
sequence in the
USER DISPLAYS
menu (between the
TARGETS
and
ACTUAL VALUES
top-level menus). The sub-menus facili-
tate text entry and Modbus register data pointer options for defining the user display content.
Once programmed, the user-definable displays can be viewed in two ways.
•
KEYPAD
: Use the MENU key to select the
USER DISPLAYS
menu item to access the first user-definable display (note
that only the programmed screens are displayed). The screens can be scrolled using the UP and DOWN keys. The
display disappears after the default message time-out period specified by the
PRODUCT SETUP
DISPLAY PROPER-
TIES
DEFAULT MESSAGE TIMEOUT
setting.
•
USER-PROGRAMMABLE CONTROL INPUT
: The user-definable displays also respond to the
INVOKE AND SCROLL
setting. Any FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate
the programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the down key and allows scrolling through the configured displays. The last display wraps up to the first
one. The
INVOKE AND SCROLL
input and the DOWN key operate concurrently.
When the default timer expires (set by the
DEFAULT MESSAGE TIMEOUT
setting), the relay will start to cycle through the
user displays. The next activity of the
INVOKE AND SCROLL
input stops the cycling at the currently displayed user dis-
play, not at the first user-defined display. The
INVOKE AND SCROLL
pulses must last for at least 250 ms to take effect.
USER-DEFINABLE
DISPLAYS
INVOKE AND SCROLL:
Off
Range: FlexLogic operand
MESSAGE
USER DISPLAY 1
Range: up to 20 alphanumeric characters
MESSAGE
USER DISPLAY 3
Range: up to 20 alphanumeric characters
MESSAGE
USER DISPLAY 2
Range: up to 20 alphanumeric characters
↓
MESSAGE
USER DISPLAY 16
Range: up to 20 alphanumeric characters
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...