B-18
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Source Energy Metering (Read Only Non-Volatile) (6 modules)
1D00
Source 1 Positive Watthour
0 to 1000000000000
Wh
0.001
F060
0
1D02
Source 1 Negative Watthour
0 to 1000000000000
Wh
0.001
F060
0
1D04
Source 1 Positive Varhour
0 to 1000000000000
varh
0.001
F060
0
1D06
Source 1 Negative Varhour
0 to 1000000000000
varh
0.001
F060
0
1D08
Reserved (8 items)
---
---
---
F001
0
1D10
...Repeated for Source 2
1D20
...Repeated for Source 3
1D30
...Repeated for Source 4
1D40
...Repeated for Source 5
1D50
...Repeated for Source 6
Energy Commands (Read/Write Command)
1D60
Energy Clear Command
0 to 1
---
1
F126
0 (No)
Source Frequency (Read Only) (6 modules)
1D80
Frequency for Source 1
2 to 90
Hz
0.001
F003
0
1D82
Frequency for Source 2
2 to 90
Hz
0.001
F003
0
1D84
Frequency for Source 3
2 to 90
Hz
0.001
F003
0
1D86
Frequency for Source 4
2 to 90
Hz
0.001
F003
0
1D88
Frequency for Source 5
2 to 90
Hz
0.001
F003
0
1D8A
Frequency for Source 6
2 to 90
Hz
0.001
F003
0
Source Demand (Read Only) (6 modules)
1E00
Source 1 Demand Ia
0 to 999999.999
A
0.001
F060
0
1E02
Source 1 Demand Ib
0 to 999999.999
A
0.001
F060
0
1E04
Source 1 Demand Ic
0 to 999999.999
A
0.001
F060
0
1E06
Source 1 Demand Watt
0 to 999999.999
W
0.001
F060
0
1E08
Source 1 Demand Var
0 to 999999.999
var
0.001
F060
0
1E0A
Source 1 Demand Va
0 to 999999.999
VA
0.001
F060
0
1E0C
Reserved (4 items)
---
---
---
F001
0
1E10
...Repeated for Source 2
1E20
...Repeated for Source 3
1E30
...Repeated for Source 4
1E40
...Repeated for Source 5
1E50
...Repeated for Source 6
Source Demand Peaks (Read Only Non-Volatile) (6 modules)
1E80
Source 1 Demand Ia Maximum
0 to 999999.999
A
0.001
F060
0
1E82
Source 1 Demand Ia Maximum Date
0 to 4294967295
---
1
F050
0
1E84
Source 1 Demand Ib Maximum
0 to 999999.999
A
0.001
F060
0
1E86
Source 1 Demand Ib Maximum Date
0 to 4294967295
---
1
F050
0
1E88
Source 1 Demand Ic Maximum
0 to 999999.999
A
0.001
F060
0
1E8A
Source 1 Demand Ic Maximum Date
0 to 4294967295
---
1
F050
0
1E8C
Source 1 Demand Watt Maximum
0 to 999999.999
W
0.001
F060
0
1E8E
Source 1 Demand Watt Maximum Date
0 to 4294967295
---
1
F050
0
1E90
Source 1 Demand Var
0 to 999999.999
var
0.001
F060
0
1E92
Source 1 Demand Var Maximum Date
0 to 4294967295
---
1
F050
0
1E94
Source 1 Demand Va Maximum
0 to 999999.999
VA
0.001
F060
0
1E96
Source 1 Demand Va Maximum Date
0 to 4294967295
---
1
F050
0
1E98
Reserved (8 items)
---
---
---
F001
0
1EA0
...Repeated for Source 2
1EC0
...Repeated for Source 3
1EE0
...Repeated for Source 4
1F00
...Repeated for Source 5
1F20
...Repeated for Source 6
Breaker Flashover (Read/Write Setting) (2 modules)
2196
Breaker Flashover 1 Function
0 to 1
---
1
F102
0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 10 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...