GE Multilin
T60 Transformer Protection System
A-1
APPENDIX A
A.1 PARAMETER LISTS
A
Appendices
APPENDIX A FlexAnalog and FlexInteger ParametersA.1Parameter Lists
A.1.1 FLEXANALOG ITEMS
A FlexAnalog parameter is an analog parameter.
FlexAnalog items are also viewable in a web browser. Enter the IP address of the UR, access the
Device Information
Menu
option, then the
FlexAnalog Parameter Listing
option. Entries displayed online depend on order code.
Table A–1: FLEXANALOG DATA ITEMS (Sheet 1 of 26)
ADDRESS
FLEXANALOG NAME
UNITS
DESCRIPTION
5792
RGF 1 Igd Mag
Amps
Restricted ground fault 1 differential ground current magnitude
5794
RGF 1 Igr Mag
Amps
Restricted ground fault 1 restricted ground current magnitude
5796
RGF 2 Igd Mag
Amps
Restricted ground fault 2 differential ground current magnitude
5798
RGF 2 Igr Mag
Amps
Restricted ground fault 2 restricted ground current magnitude
5800
RGF 3 Igd Mag
Amps
Restricted ground fault 3 differential ground current magnitude
5802
RGF 3 Igr Mag
Amps
Restricted ground fault 3 restricted ground current magnitude
5804
RGF 4 Igd Mag
Amps
Restricted ground fault 4 differential ground current magnitude
5806
RGF 4 Igr Mag
Amps
Restricted ground fault 4 restricted ground current magnitude
5808
RGF 5 Igd Mag
Amps
Restricted ground fault 5 differential ground current magnitude
5810
RGF 5 Igr Mag
Amps
Restricted ground fault 5 restricted ground current magnitude
5812
RGF 6 Igd Mag
Amps
Restricted ground fault 6 differential ground current magnitude
5814
RGF 6 Igr Mag
Amps
Restricted ground fault 6 restricted ground current magnitude
5824
Field RTD 1 Value
---
Field RTD 1 value
5825
Field RTD 2 Value
---
Field RTD 2 value
5826
Field RTD 3 Value
---
Field RTD 3 value
5827
Field RTD 4 Value
---
Field RTD 4 value
5828
Field RTD 5 Value
---
Field RTD 5 value
5829
Field RTD 6 Value
---
Field RTD 6 value
5830
Field RTD 7 Value
---
Field RTD 7 value
5831
Field RTD 8 Value
---
Field RTD 8 value
5832
Field TDR 1 Value
---
Field TDR 1 value
5834
Field TDR 2 Value
---
Field TDR 2 value
5836
Field TDR 3 Value
---
Field TDR 3 value
5838
Field TDR 4 Value
---
Field TDR 4 value
5840
Field TDR 5 Value
---
Field TDR 5 value
5842
Field TDR 6 Value
---
Field TDR 6 value
5844
Field TDR 7 Value
---
Field TDR 7 value
5846
Field TDR 8 Value
---
Field TDR 8 value
5856
Freq Rate 1 Value
Hz/s
Frequency rate of change 1 actual value
5860
Freq Rate 2 Value
Hz/s
Frequency rate of change 2 actual value
5864
Freq Rate 3 Value
Hz/s
Frequency rate of change 3 actual value
5868
Freq Rate 4 Value
Hz/s
Frequency rate of change 4 actual value
6144
SRC 1 Ia RMS
Amps
Source 1 phase A current RMS
6146
SRC 1 Ib RMS
Amps
Source 1 phase B current RMS
6148
SRC 1 Ic RMS
Amps
Source 1 phase C current RMS
6150
SRC 1 In RMS
Amps
Source 1 neutral current RMS
6152
SRC 1 Ia Mag
Amps
Source 1 phase A current magnitude
6154
SRC 1 Ia Angle
Degrees
Source 1 phase A current angle
6155
SRC 1 Ib Mag
Amps
Source 1 phase B current magnitude
6157
SRC 1 Ib Angle
Degrees
Source 1 phase B current angle
6158
SRC 1 Ic Mag
Amps
Source 1 phase C current magnitude
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...