GE Multilin
T60 Transformer Protection System
5-43
5 SETTINGS
5.2 PRODUCT SETUP
5
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
The main transmission menu is shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
sets the time between GSSE or GOOSE messages when there are no remote out-
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state
heartbeat
time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
setting is applicable to GSSE, fixed T60 GOOSE, and configurable GOOSE.
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
GSEE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
GSSE ID
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
string identifies the GSSE message to the receiving device. In T60 releases previous to 5.0x, this name string was repre-
sented by the
RELAY NAME
setting.
GSSE / GOOSE
CONFIGURATION
TRANSMISSION
MESSAGE
RECEPTION
TRANSMISSION
GENERAL
MESSAGE
GSSE
MESSAGE
FIXED GOOSE
MESSAGE
CONFIGURABLE
GOOSE
GENERAL
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
Range: 1 to 60 s in steps of 1
GSSE
GSSE FUNCTION:
Enabled
Range: Enabled, Disabled
MESSAGE
GSSE ID:
GSSEOut
Range: 65-character ASCII string
MESSAGE
DESTINATION MAC:
000000000000
Range: standard MAC address
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...