GE Multilin
T60 Transformer Protection System
5-93
5 SETTINGS
5.2 PRODUCT SETUP
5
The G.703 modules are fixed at 64 kbps. The
DIRECT I/O DATA RATE
setting is not applicable to these modules.
The
DIRECT I/O CHANNEL CROSSOVER
setting applies to T60s with dual-channel communication cards and allows crossing
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. See the
Inputs
and Outputs
section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.
Table 5–12: DIRECT INPUT AND OUTPUT DATA RATES
MODULE
CHANNEL
SUPPORTED DATA RATES
74
Channel 1
64 kbps
Channel 2
64 kbps
7L
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7M
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7P
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7T
Channel 1
64 kbps, 128 kbps
7W
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7V
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
2A
Channel 1
64 kbps
2B
Channel 1
64 kbps
Channel 2
64 kbps
2G
Channel 1
128 kbps
2H
Channel 1
128 kbps
2I
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
2J
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
76
Channel 1
64 kbps
77
Channel 1
64 kbps
Channel 2
64 kbps
75
Channel 1
64 kbps
Channel 2
64 kbps
7E
Channel 1
64 kbps
Channel 2
64 kbps
7F
Channel 1
64 kbps
Channel 2
64 kbps
7G
Channel 1
64 kbps
Channel 2
64 kbps
7Q
Channel 1
64 kbps
Channel 2
64 kbps
7R
Channel 1
64 kbps
7S
Channel 1
64 kbps
Channel 2
64 kbps
NOTE
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...