B-98
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F500
UR_UINT16: PACKED BITFIELD
First register indicates input/output state with bits 0 (MSB) to 15
(LSB) corresponding to input/output state 1 to 16. The second reg-
ister indicates input/output state with bits 0 to 15 corresponding to
input/output state 17 to 32 (if required). The third register indicates
input/output state with bits 0 to 15 corresponding to input/output
state 33 to 48 (if required). The fourth register indicates input/out-
put state with bits 0 to 15 corresponding to input/output state 49 to
64 (if required).
The number of registers required is determined by the specific
data item. A bit value of 0 = Off and 1 = On.
F501
UR_UINT16: LED STATUS
Low byte of register indicates LED status with bit 0 representing
the top LED and bit 7 the bottom LED. A bit value of 1 indicates
the LED is on, 0 indicates the LED is off.
0 = Off, 1 = On
F502
BITFIELD: ELEMENT OPERATE STATES
Each bit contains the operate state for an element. See the F124
format code for a list of element IDs. The operate bit for element ID
X is bit [X mod 16] in register [X/16].
F513
ENUMERATION: POWER SWING MODE
0 = Two Step, 1 = Three Step
F514
ENUMERATION: POWER SWING TRIP MODE
0 = Delayed, 1 = Early
F515
ENUMERATION ELEMENT INPUT MODE
0 = Signed, 1 = Absolute
F516
ENUMERATION ELEMENT COMPARE MODE
0 = Level, 1 = Delta
F517
ENUMERATION: ELEMENT DIRECTION OPERATION
0 = Over, 1 = Under
F518
ENUMERATION: FLEXELEMENT UNITS
0 = Milliseconds, 1 = Seconds, 2 = Minutes
F519
ENUMERATION: NON-VOLATILE LATCH
0 = Reset-Dominant, 1 = Set-Dominant
F521
ENUMERATION: GROUND DISTANCE POLARIZING CURRENT
0 = Zero-Sequence; 1 = Negative-Sequence
F522
ENUMERATION: TRANSDUCER DCmA OUTPUT RANGE
0 = –1 to 1 mA, 1 = 0 to 1 mA, 2 = 4 to 20 mA
F523
ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULT
VARIATION
F524
ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION
F525
ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION
Bitmask
Default variation
0
1
1
2
2
5
3
6
Bitmask
Default variation
0
1
1
2
2
9
3
10
Bitmask
Default variation
0
1
1
2
2
3
3
4
4
5
5
7
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...