5.9 TRANSDUCER INPUTS AND OUTPUTS
5 SETTINGS
5
It is recommended to use the T60 to configure the RRTD parameters. If the RRTDPC software is used to change the RRTD
settings directly (the application and type settings), then one of the following two operations is required for changes to be
reflected in the T60.
•
Cycle power to T60.
•
Break then re-establish the communication link between the RRTD unit and the T60. This will cause the
RRTD COMM
FAIL
operand to be asserted then de-asserted.
b) REMOTE RTDS 1 THROUGH 12
PATH: SETTINGS
TRANSDUCER I/O
RRTD INPUTS
RRTD RTD 1(12)
The remote RTD inputs convert values of input resistance into temperature for further operations. These inputs are
intended to be connected to any of the RTD types in common use. Specific hardware details are contained in chapter 3.
On power up, the T60 reads and saves all application and type settings from the RRTD. This synchronizes the RRTD and
T60. Any changes to RRTD settings (function, application, or type) from the T60 interface are immediately reflected in the
RRTD. The following rules are followed.
•
If the
RRTD 1 FUNCTION
setting is “Enabled”, then the
RRTD 1 APPLICATION
setting value will be written to RRTD device.
•
If the
RRTD 1 FUNCTION
setting is “Disabled”, then
RRTD1 APPLICATION
setting value is set as “None”.
•
If the
RRTD 1 APPLICATION
or
RRTD 1 TYPE
settings are changes, then these settings are immediately written to the
RRTD device.
RRTD 1
RRTD 1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
RRTD 1 ID:
RRTD 1
Range: Up to 20 alphanumeric characters
MESSAGE
RRTD 1 TYPE:
100
Ω
Platinum
Range: 100
Ω
Nickel, 10
Ω
Copper, 100
Ω
Platinum,
120
Ω
Nickel
MESSAGE
RRTD 1
APPLICATION: None
Range: None, Stator, Bearing, Ambient, Group 1,
Group 2
MESSAGE
RRTD 1 ALARM
TEMPERATURE: 130°C
Range: 1 to 200°C in steps of 1
MESSAGE
RRTD 1 ALARM
PKP DELAY: 5 s
Range: 5 to 600 s in steps of 5
MESSAGE
RRTD 1 TRIP
TEMPERATURE: 130°C
Range: 1 to 200°C in steps of 1
MESSAGE
RRTD 1 TRIP
PKP DELAY: 5 s
Range: 5 to 600 s in steps of 5
MESSAGE
RRTD 1 TRIP
RST DELAY: 5 s
Range: 5 to 600 s in steps of 5
MESSAGE
RRTD 1 TRIP VOTING:
None
Range: None, Group, Remote RTD 1, Remote RTD 2,...,
Remote RTD 12
MESSAGE
RRTD 1 OPEN:
None
Range: None, Alarm, Block
MESSAGE
RRTD 1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
RRTD 1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
RRTD 1 EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...