GE Multilin
T60 Transformer Protection System
5-277
5 SETTINGS
5.7 CONTROL ELEMENTS
5
Figure 5–138: ACKNOWLEDGE MODE
APPLICATION EXAMPLE
Consider an application where the selector switch is used to control setting groups 1 through 4 in the relay. The setting
groups are to be controlled from both user-programmable pushbutton 1 and from an external device via contact inputs 1
through 3. The active setting group shall be available as an encoded three-bit word to the external device and SCADA via
output contacts 1 through 3. The pre-selected setting group shall be applied automatically after 5 seconds of inactivity of
the control inputs. When the relay powers up, it should synchronize the setting group to the three-bit control input.
Make the following changes to setting group control in the
SETTINGS
CONTROL ELEMENTS
SETTING GROUPS
menu:
SETTING GROUPS FUNCTION:
“Enabled”
GROUP 4 ACTIVATE ON:
“SELECTOR 1 POS 4"
SETTING GROUPS BLK:
“Off”
GROUP 5 ACTIVATE ON:
“Off”
GROUP 2 ACTIVATE ON:
“SELECTOR 1 POS 2"
GROUP 6 ACTIVATE ON:
“Off”
GROUP 3 ACTIVATE ON:
“SELECTOR 1 POS 3"
Make the following changes to selector switch element in the
SETTINGS
CONTROL ELEMENTS
SELECTOR SWITCH
SELECTOR SWITCH 1
menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:
842736A1.CDR
STEP-UP
ACK
3BIT A0
3BIT A1
3BIT A2
3BIT ACK
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6
POS 7
BIT 0
BIT 1
BIT 2
pre-existing
position 2
changed to 4 with
a pushbutton
changed to 1 with
a 3-bit input
changed to 2 with
a pushbutton
STP ALARM
BIT ALARM
ALARM
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...