GE Multilin
T60 Transformer Protection System
B-45
APPENDIX B
B.4 MEMORY MAPPING
B
7052
...Repeated for Phase Overvoltage 3
Phase Distance (Read/Write Grouped Setting) (5 modules)
7070
Phase Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
7071
Phase Distance Zone 1 Current Supervision
0.05 to 30
pu
0.001
F001
200
7072
Phase Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
7073
Phase Distance Zone 1 Direction
0 to 2
---
1
F154
0 (Forward)
7074
Phase Distance Zone 1 Comparator Limit
30 to 90
degrees
1
F001
90
7075
Phase Distance Zone 1 Delay
0 to 65.535
s
0.001
F001
0
7076
Phase Distance Zone 1 Block
0 to 4294967295
---
1
F300
0
7078
Phase Distance Zone 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7079
Phase Distance Zone 1 Events
0 to 1
---
1
F102
0 (Disabled)
707A
Phase Distance Zone 1 Shape
0 to 1
---
1
F120
0 (Mho)
Fixed in G60
707B
Phase Distance Zone 1 RCA
30 to 90
degrees
1
F001
85
707C
Phase Distance Zone 1 DIR RCA
30 to 90
degrees
1
F001
85
707D
Phase Distance Zone 1 DIR Comp Limit
30 to 90
degrees
1
F001
90
707E
Phase Distance Zone 1 Quad Right Blinder
0.02 to 500
ohms
0.01
F001
1000
707F
Phase Distance Zone 1 Quad Right Blinder RCA
60 to 90
degrees
1
F001
85
7080
Phase Distance Zone 1 Quad Left Blinder
0.02 to 500
ohms
0.01
F001
1000
7081
Phase Distance Zone 1 Quad Left Blinder RCA
60 to 90
degrees
1
F001
85
7082
Phase Distance Zone 1 Volt Limit
0 to 5
pu
0.001
F001
0
7083
Phase Distance Zone 1 Transformer Voltage Connection
0 to 12
---
1
F153
0 (None)
7084
Phase Distance Zone 1 Transformer Current Connection
0 to 12
---
1
F153
0 (None)
7085
Phase Distance Zone 1 Rev Reach
0.02 to 500
ohms
0.01
F001
200
7086
Phase Distance Zone 1 Rev Reach RCA
30 to 90
degrees
1
F001
85
7087
Reserved (10 items)
---
---
---
F001
0
7091
...Repeated for Phase Distance Zone 2
70B2
...Repeated for Phase Distance Zone 3
70D3
...Repeated for Phase Distance Zone 4
70F4
...Repeated for Phase Distance Zone 5
Ground Distance (Read/Write Grouped Setting) (5 modules)
7130
Ground Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
7131
Ground Distance Zone 1 Current Supervision
0.05 to 30
pu
0.001
F001
200
7132
Ground Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
7133
Ground Distance Zone 1 Direction
0 to 2
---
1
F154
0 (Forward)
7134
Ground Distance Zone 1 Comparator Limit
30 to 90
degrees
1
F001
90
7135
Ground Distance Zone 1 Delay
0 to 65.535
s
0.001
F001
0
7136
Ground Distance Zone 1 Block
0 to 4294967295
---
1
F300
0
7138
Ground Distance Zone 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7139
Ground Distance Zone 1 Events
0 to 1
---
1
F102
0 (Disabled)
713A
Ground Distance Zone 1 Shape
0 to 1
---
1
F120
0 (Mho)
713B
Ground Distance Zone 1 Z0 Z1 Magnitude
0 to 10
---
0.01
F001
270
713C
Ground Distance Zone 1 Z0 Z1 Angle
-90 to 90
degrees
1
F002
0
713D
Ground Distance Zone 1 RCA
30 to 90
degrees
1
F001
85
713E
Ground Distance Zone 1 DIR RCA
30 to 90
degrees
1
F001
85
713F
Ground Distance Zone 1 DIR Comp Limit
30 to 90
degrees
1
F001
90
7140
Ground Distance Zone 1 Quad Right Blinder
0.02 to 500
ohms
0.01
F001
1000
7141
Ground Distance Zone 1 Quad Right Blinder RCA
60 to 90
degrees
1
F001
85
7142
Ground Distance Zone 1 Quad Left Blinder
0.02 to 500
ohms
0.01
F001
1000
7143
Ground Distance Zone 1 Quad Left Blinder RCA
60 to 90
degrees
1
F001
85
7144
Ground Distance Zone 1 Z0M Z1 Magnitude
0 to 7
---
0.01
F001
0
7145
Ground Distance Zone 1 Z0M Z1 Angle
-90 to 90
degrees
1
F002
0
7146
Ground Distance Zone 1 Voltage Level
0 to 5
pu
0.001
F001
0
7147
Ground Distance Zone 1 Non-Homogeneous Angle
-40 to 40
degrees
0.1
F002
0
Table B–10: MODBUS MEMORY MAP (Sheet 37 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...