5-192
T60 Transformer Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
c) GROUND DISTANCE
(ANSI 21G)
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
DISTANCE
GROUND DISTANCE Z1(Z5)
GROUND DISTANCE Z1
GND DIST Z1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
GND DIST Z1 DIR:
Forward
Range: Forward, Reverse, Non-directional
MESSAGE
GND DIST Z1
SHAPE: Mho
Range: Mho, Quad
MESSAGE
GND DIST Z1
Z0/Z1 MAG: 2.70
Range: 0.00 to 10.00 in steps of 0.01
MESSAGE
GND DIST Z1
Z0/Z1 ANG: 0°
Range: –90 to 90° in steps of 1
MESSAGE
GND DIST Z1
ZOM/Z1 MAG: 0.00
Range: 0.00 to 7.00 in steps of 0.01
MESSAGE
GND DIST Z1
ZOM/Z1 ANG: 0°
Range: –90 to 90° in steps of 1
MESSAGE
GND DIST Z1
REACH: 2.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1
RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 REV
REACH: 2.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 REV
REACH RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 POL
CURRENT: Zero-seq
Range: Zero-seq, Neg-seq
MESSAGE
GND DIST Z1 NON-
HOMOGEN ANG: 0.0°
Range: –40.0 to 40.0° in steps of 0.1
MESSAGE
GND DIST Z1
COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1
DIR RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1
DIR COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 QUAD
RGT BLD: 10.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 QUAD
RGT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
GND DIST Z1 QUAD
LFT BLD: 10.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 QUAD
LFT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
GND DIST Z1
SUPV: 0.200 pu
Range: 0.050 to 30.000 pu in steps of 0.001
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...